EasyManua.ls Logo

NuAire Ecosmart ESTCP - User Manual

NuAire Ecosmart ESTCP
6 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Nuaire Limited Western Industrial Estate Caerphilly United Kingdom CF83 1NA
T: 029 2085 8400 F: 029 2085 8444 E: info@nuaire.co.uk W: www.nuaire.co.uk
Fig. 1 View of a typical unit.
ESTCP-R & ESXCP-R, ESTCP-B, & ESXCP-B
Fig. 2 View of a typical unit.
Introduction
The Nuaire range of constant pressure direct drive external
units consists of single and twinfan models with duties up
to a maximum of 1.5m
3
/s. Twinfan units incorporate
run/standby and auto changeover features whereas the
single fan units have one fan only. Coding is as follows:
ESTCP-X and ESXCP-X are ‘in-line’ units supplied with rigid
circular spigots at each end and are suited to external and
internal duct mounted applications.
ESTCP-R and ESXCP-R are supplied with rigid circular inlet
spigot and two opposed side discharge spigots, suited to
external roof mounted applications.
ESTCP-B and ESXCP-B are supplied with rigid circular inlet
spigot and two opposed side discharge spigots, suited to
external roof mounted applications.
Casings are manufactured from heavy gauge ‘Aluzinc’
aluminium and zinc coated mild steel. Full size access panels
are fitted to the top of the units. These panels are fully
detachable for inspection and connection purposes. The units
incorporate two independent motors with high efficiency,
centrifugal impellers running in metal scrolls.
The motors are manufactured to BS 5000 and are suitable
for single phase supply. Airflow and failure monitors are
standard as is Class B insulation. The units are suitable for
operation in ambient temperatures up to 40
o
C.
Handling
Handle the units carefully to avoid damage and distortion.
If mechanical aids are used to lift the unit, spreaders should
be employed and positioned so as to prevent the slings,
webbing etc. making contact with the casing.
Installation
The installation must be carried out by competent
personnel in accordance with the appropriate authority
and conforming to all statutory and governing regulations.
The units are suitable for internal or external use. All units
can be installed at any angle up to 60
o
. However, on a
sloping roof the unit must be blowing upwards toward
the roof ridge to ensure correct backdraught shutter
operation.
Units should always be positioned with sufficient space
to allow removal of the access cover and subsequent
removal of fan and motor assemblies etc.
Whether internally or externally mounted, the method of
fixing is the responsibility of the installer.
All units have a bottom skirt to allow for fixing directly onto a
suitably sized curb or builders upstand. Nuaire can supply a
matching prefabricated curb for these units. Details of
curbs and dimensions for a suitable external concrete
upstand are shown on page 2. Ductwork connections must
be airtight to prevent any loss of performance.
All units have an internal connection box requiring connection
to the mains supply on installation. It is the installers
responsibility to drill the case to provide access for the
electrical cables. Care should be taken not to damage internal
components and the cable entry should be properly sealed.
External
Commissioning box
D
C
A
B
Removable
top panel
Control module
located internally
Weight (kg)
Unit AB CD dia. EST ESX
ESTCP4-X 1165 980 575 250 85 -
ESTCP6-X/ESXCP6-X 1165 980 575 400 86 70
ESTCP9-X/ESXCP9-X 1495 1125 710 500 162 133
Table 1. Dimensions (mm)
Weight (kg)
Unit AB CD dia. EFEST ESX
ESTCP4-R 1165 980 575 250 --85 -
ESTCP4-B 1165 980 575 - 152 305 85 -
ESTCP6-R/ESXCP6-R 1165 980 575 400 --86 70
ESTCP6-B/ESXCP6-B 1165 980 575 - 229 457 86 70
ESTCP9-R/ESXCP9-R 1495 1125 710 500 --162 133
ESTCP9-B/ESXCP9-B 1495 1125 710 - 304 762 162 133
A
B
Removable
top panel
Commissioning box
Opposed
outlet
grille
Circular inlet
spigot on end
of unit
Code: ESTCP*-R
D
E
F
Control module
located internally
C
Rectangular
bottom inlet spigot
ESTCP*- B only
Table 2. Dimensions (mm)
ESTCP-X & ESXCP-X
1
21. 10. 16. Leaflet Number 671171
Constant Pressure, Single phase,
Direct Drive Single & Twinfan Units
For external use only
Installation and
Maintenance
The EMC Directive
2014/30/EU
The Low Voltage
directive
2014/35/EU
Models
ESTCP & ESXCP
Question and Answer IconNeed help?

Do you have a question about the NuAire Ecosmart ESTCP and is the answer not in the manual?

Summary

Introduction to Nuaire Constant Pressure Units

Product Unit Types

Details on ESTCP-X/ESXCP-X (in-line) and ESTCP-R/ESXCP-R/ESTCP-B/ESXCP-B (roof mounted) unit configurations.

Handling and Installation Procedures

General Handling Guidelines

Instructions for careful handling to avoid damage and distortion during unit manipulation.

Installation Requirements

Guidance on competent installation, unit positioning, and ductwork connections.

Prefabricated Curb and Roof Mounting

Details on using prefabricated curbs and roof upstand mounting for secure unit placement.

Controlling Static Pressure

Methods for managing static pressure at the fan inlet for optimal system performance.

Electrical Details and Wiring

Wiring Connections and Control

Covers control module connections, signals (fault/run), damper connections, and data cable installation.

Motor Electrical Information

Technical data for fan motors including speed, power, current, fuse ratings, and operating pressure.

Commissioning Panel and Settings

LED Indicators and BMS Input

Explanation of LED indicators on the control panel and response to BMS signals.

Setting Fan Speed and Operating Pressure

Procedures for adjusting maximum/minimum fan speed and system operating pressure.

Maintenance, Parts, and Warranty

Maintenance Intervals and Lubrication

Recommended maintenance schedule and confirmation that motors have sealed-for-life bearings.

General Cleaning and Inspection

Steps for cleaning the fan unit exterior, interior, fan, and motor assemblies.

Replacement of Parts and Warranty

Guidance on replacing fan/motor assemblies and details of the 5-year warranty.

After Sales Enquiries

Contact information for technical assistance, spare parts, and product information.

Declaration and Safety Information

Declaration of Incorporation

Formal statement regarding machinery assembly and conformity with EC directives.

Safe Installation and Operation Guidelines

Comprehensive information for safe installation, commissioning, operation, and maintenance.

Summary

Introduction to Nuaire Constant Pressure Units

Product Unit Types

Details on ESTCP-X/ESXCP-X (in-line) and ESTCP-R/ESXCP-R/ESTCP-B/ESXCP-B (roof mounted) unit configurations.

Handling and Installation Procedures

General Handling Guidelines

Instructions for careful handling to avoid damage and distortion during unit manipulation.

Installation Requirements

Guidance on competent installation, unit positioning, and ductwork connections.

Prefabricated Curb and Roof Mounting

Details on using prefabricated curbs and roof upstand mounting for secure unit placement.

Controlling Static Pressure

Methods for managing static pressure at the fan inlet for optimal system performance.

Electrical Details and Wiring

Wiring Connections and Control

Covers control module connections, signals (fault/run), damper connections, and data cable installation.

Motor Electrical Information

Technical data for fan motors including speed, power, current, fuse ratings, and operating pressure.

Commissioning Panel and Settings

LED Indicators and BMS Input

Explanation of LED indicators on the control panel and response to BMS signals.

Setting Fan Speed and Operating Pressure

Procedures for adjusting maximum/minimum fan speed and system operating pressure.

Maintenance, Parts, and Warranty

Maintenance Intervals and Lubrication

Recommended maintenance schedule and confirmation that motors have sealed-for-life bearings.

General Cleaning and Inspection

Steps for cleaning the fan unit exterior, interior, fan, and motor assemblies.

Replacement of Parts and Warranty

Guidance on replacing fan/motor assemblies and details of the 5-year warranty.

After Sales Enquiries

Contact information for technical assistance, spare parts, and product information.

Declaration and Safety Information

Declaration of Incorporation

Formal statement regarding machinery assembly and conformity with EC directives.

Safe Installation and Operation Guidelines

Comprehensive information for safe installation, commissioning, operation, and maintenance.

Overview

The Nuaire range of constant pressure direct drive external units comprises single and twin-fan models, designed for duties up to a maximum of 1.5m³/s. Twin-fan units incorporate run/standby and auto changeover features, while single-fan units have one fan only.

Function Description

The ESTCP-X and ESXCP-X models are 'in-line' units, supplied with rigid circular spigots at each end, making them suitable for external and internal duct-mounted applications.

The ESTCP-R and ESXCP-R models are supplied with a rigid circular inlet spigot and two opposed side discharge spigots, designed for external roof-mounted applications.

The ESTCP-B and ESXCP-B models are supplied with a rigid circular inlet spigot and two opposed side discharge spigots, also suited for external roof-mounted applications.

The casings are constructed from heavy gauge 'Aluzinc' aluminium and zinc-coated mild steel. Full-size access panels are fitted to the top of the units, which are fully detachable for inspection and connection purposes. The units incorporate two independent motors with high-efficiency, centrifugal impellers running in metal scrolls.

The motors are manufactured to BS 5000 and are suitable for single-phase supply. Airflow and failure monitors are standard, as is Class B insulation. The units are suitable for operation in ambient temperatures up to 40°C.

Ecosmart constant pressure extract fans are supplied to control the static pressure at the fan inlet. This setup is suitable for the majority of applications. However, when ancillaries with high pressure losses are fitted to the fan's inlet side, the low pressure tapping needs to be moved from the fan chamber to a location upstream of the ancillaries. Failure to do this will result in excessive pressure being applied to the dampers at the rooms when the system is running in trickle mode.

The fan's response to a 0-10V dc BMS signal is given in the following table. The BMS signal will override any sensors and user control connected in the system.

Usage Features

Handling: Handle the units carefully to avoid damage and distortion. If mechanical aids are used to lift the unit, spreaders should be employed and positioned so as to prevent the slings, webbing, etc., from making contact with the casing.

Installation: The installation must be carried out by competent personnel in accordance with the appropriate authority and conforming to all statutory and governing regulations. The units are suitable for internal or external use. All units can be installed at any angle up to 60°. However, on a sloping roof, the unit must be blowing upwards toward the roof ridge to ensure correct backdraught shutter operation.

Units should always be positioned with sufficient space to allow removal of the access cover and subsequent removal of fan and motor assemblies. Whether internally or externally mounted, the method of fixing is the responsibility of the installer.

All units have a bottom skirt to allow for fixing directly onto a suitably sized curb or builders upstand. Nuaire can supply a matching prefabricated curb for these units. Ductwork connections must be airtight to prevent any loss of performance.

All units have an internal connection box requiring connection to the mains supply on installation. It is the installer's responsibility to drill the case to provide access for the electrical cables. Care should be taken not to damage internal components, and the cable entry should be properly sealed.

A commissioning box is provided on the outside of the case. The unit should be securely screwed to its curb or mounting to prevent vibration and/or wind damage. Note that on the bottom inlet (ESTCP-B/ESXCP-B) units, the cabling could be carried up from inside the building through the bottom inlet spigot.

Prefabricated curbs, manufactured in pre-galvanised steel, reduce design work and guarantee correct unit mounting on site. The upper faces of the curb are fitted with a robust sealing strip.

Roof Upstand Mounting: The fan casings have an inside skirt depth of 60mm or, in the case of the largest size units only, 50mm. It is recommended that the units are mounted upon a suitable curb or upstand which has a minimum height of 150mm (inclusive of the timber capping if applicable). This mounting height provides adequate distance to avoid any standing water on the roof being drawn into the fan (this can occur on bottom inlet installations if a unit is not properly installed and an air leak in the unit/ductwork joint is pulling air over the curb). The recommended height will also ensure that the unit does not 'stand' on its skirt edge.

Electrical Details: Before commencing work, ensure that the unit, switched live, and Nuaire control are electrically isolated from the mains supply. An Inverter is used to provide speed control. When the fan is isolated, allow 5 minutes for the capacitors in the inverter to discharge before commencing any work on the unit. If an RCD is fitted to protect the circuit, a type B RCD should be used (trip limit 300mA). Otherwise, nuisance tripping will occur.

The 4 IDC plug-in connectors are provided for the connection of compatible sensors, manual controls, and for linking the fans together under a common control. If more than 4 connections are required, a junction box should be used. A signal of 100-230V a.c. will activate the fan. Note that a signal from an isolating transformer will produce an unpredictable result and is not recommended.

Damper Connections:

  • OP - 230V 50Hz 1A max supply to open the damper
  • CL - 230V 50Hz 1A max supply to close the damper
  • N - Neutral supply to damper
  • RET - 230V ac return signal from the damper limit switch to indicate the damper has reached its operating position. If the return signal is not present, the fan will wait for 1 minute before starting.
  • Note: If a damper is not fitted, connect a link wire from OP to RET. This will cancel the delay.

Volt Free Relay Contacts: The volt free contacts are not fused. If these are used to power any external equipment, the installer must provide adequate fusing or other protections. These contacts are rated at 5A resistive, 0.5A inductive.

Run connections: These contacts are closed when the fan is running. Fault connections: No fault = the contacts are closed. Fault = the contacts are opened (this includes no power supply at the unit).

Data Cable Installation: A 4-core SELV data cable is used to connect devices such as sensors to the fan and for interconnecting multiple fan units. Do not run data cable in the same conduit as the mains cables and ensure there is a 50mm separation between the data cable and other cables. The maximum cable run between any two devices is 300m when it is installed in accordance with the instructions. Please note that the total data cable length used in any system must be less than 1000m. Keep the number of cable joints to a minimum to ensure the best data transmission efficiency between devices.

Maximum Number of Devices: The maximum number of devices (including fans) that can be connected together via the data cable is 32, irrespective of their functions.

Any other low voltage/signal cable connection (BMS): Follow the guidelines as given in 'd' and keep the cable length as short as possible - less than 50m.

Testing after Installation: Ensure that the Fan unit and any specified controls are fitted securely according to the instructions. Switch on the mains supply. Push the test button to run each fan and check that they run satisfactorily. If a switched live signal is used, activate this signal and check that the fan runs. De-activate the switched live signal and check the run-on-time; adjust if necessary. Adjust the maximum and minimum airflow (if required) by following the instructions on page 4.

Using the Test button: The test button allows the individual blowers within the unit to be checked for its operation. If the fan is running already, press the button once to stop the fan, press again to switch on the standby fan, press again to stop and so on. Note that the fan will return to normal operation after 30 seconds.

Setting the Maximum fan speed:

  1. This adjustment should only be made if running the fan at maximum speed would cause a problem on site.
  2. Switch off the power supply, connect a link wire between L and SL.
  3. Unplug all items connected to the 'Net' connections. Set the pressure setting to the maximum position.
  4. Switch on the power supply, allow the fan to reach a steady speed (approx. 30 seconds). Adjust the pot marked 'Max' to set the maximum speed.
  5. After setting the speed, switch off the power and reconnect the wiring.

Setting the Minimum fan speed:

  1. This adjustment should only be made if running the fan at minimum speed would cause a problem on site.
  2. Switch off the power supply, connect a link wire between L and SL.
  3. Unplug all items connected to the 'Net' connections. Set the pressure setting to the minimum position.
  4. Switch on the power supply, allow the fan to reach a steady speed (approx. 30 seconds). Adjust the pot marked Min to set the minimum speed.
  5. After setting the speed, switch off the power and reconnect the wiring.

Setting the operating pressure:

  1. Select a suitable location on the inlet side of the fan to read the static pressure of the system. This should be a straight section of ductwork, away from any obstructions or bends. Read the static pressure at this point using suitable instruments. If the control pressure tapping has been moved because of ancillaries fitted to the fan inlet, measure the static pressure at the new location.
  2. Adjust the pressure setting using the potentiometer labelled for this purpose in the commissioning box until the pressure of the system reaches the desired level.
  3. The adjustment should be made slowly and allow the system to settle (approx. 30 seconds) before reading the pressure.

Maintenance Features

Maintenance Intervals: The first maintenance should be carried out three months after commissioning and thereafter at twelve-monthly intervals. These intervals may need to be shortened if the unit is operating in adverse environmental conditions, or in heavily polluted air. Note: failure to maintain the unit as recommended will invalidate the warranty.

Lubrication: Motors are fitted with sealed-for-life bearings and do not require any lubrication.

General Cleaning and Inspection: Clean and inspect the exterior of the fan unit and associated controls, etc. Remove the access panel from the fan unit. Inspect and, if necessary, clean the fan and motor assemblies and the interior of the case. If the unit is heavily soiled, it may be more convenient to remove the fan/motor assemblies.

Check that the shutters are free to move smoothly and that they seal the appropriate fan outlet effectively. Clean and inspect each fan and motor assembly as follows, taking care not to damage, distort, or disturb the balance of the impeller:

  • Lightly brush away dirt and dust, paying particular attention to any build-up at the motor ventilating slots. If necessary, carefully remove with a blade or scraper.
  • Stubborn dirt at the impeller may be carefully removed with a stiff nylon brush.
  • Check all parts for security and general condition. Check that the impeller rotates freely.

Refit the assemblies to the unit (see Replacement of Parts) then replace the access covers. If Nuaire controls and/or remote indicators are fitted, remove the covers and carefully clean out the interiors as necessary. Check for damage. Check security of components. Refit the access covers.

Replacement of Parts: The only item of the fan units unit likely to require replacement are the fan/motor assemblies due to a failed motor or damaged impeller. In either eventuality, the complete fan/motor assembly must be removed from the unit case. Note: before commencing work, electrically isolate the fan unit and/or the associated Nuaire control, if fitted, from the mains supply.

Remove the access cover. Disconnect the incoming wiring from the connection box (located on the fan scroll) on the particular fan/motor assembly to be removed. Support the weight of the fan/motor assembly and remove the mounting screws and washers. Lift the assembly out of the case. After replacing the faulty item, refit the fan/motor assembly and reconnect the incoming wiring to the fan-mounted connection box. Replace the access cover.

Spare Parts: When ordering spares, please quote the serial number of the unit together with the part number. If the part number is not known, please give a full description of the part required. The serial number will be found on the identification plate attached to the unit casing.

Warranty: The 5-year warranty starts from the day of delivery and includes parts and labour for the first year. The remaining period covers replacement parts only. This warranty is void if the equipment is modified without authorisation, is incorrectly applied, misused, disassembled, or not installed, commissioned, and maintained in accordance with the details contained in this manual and general good practice.

NuAire Ecosmart ESTCP Specifications

General IconGeneral
CategoryFan
Housing MaterialGalvanized Steel
Motor TypeElectronically Commutated Motor (ECM)
Wheel MaterialAluminum
Energy EfficiencyHigh efficiency ECM motor

Related product manuals