3.9. Inactivity Timeouts
Timeouts are set to revert to Access Level 1 if there is not activity, and for system safety in the event that the
system is left without restoring it to Access Level 1. The following timeouts apply:
Enable Access Level passcode: No action for 20 s causes return to Access Level 1.
When in Access Level 2:
Enter Access Level 2 passcode: No action for 20 s causes return to Access Level 1.
When performing functions in Access Level 2, no manual input for 20 s causes the process to be
cancelled. The control and indicating equipment will return to Access Level 2.
With no specific function selected, no manual input for 1 h causes return to Access Level 1.
When in Access Level 3:
Enter Access Level 3 passcode: No action for 20 s causes return to Access Level 1.
No activity (eg a button press) for 1 h causes return to Access Level 1.
When in Device Test mode, no activity for 4 h causes return to Access Level 1.