INSTRUCTIONS OJ-DV | Installation
13. Electrical installation
Warning
OJ-DV must only be installed and commissioned by trained/qualified personnel.
Check that the data specified on the rating plate of the motor matches the data specified on the
OJ-DV rating plate.
Incorrect electrical installation may cause a risk of severe or fatal personal injury.
Warning
13.1 Dangerous induced voltage (Windmilling)
If natural drafts through the duct system cause the fan to rotate even when it has not received an
operating signal (called windmilling), there is a risk that the motor will induce voltage on the OJ-DV
motor terminals, making them dangerous to touch.
Caution
13.2 EMC-compliant installation
Always use shielded cables as motor cables.
Shielded cable is not necessary for I/O signal cables and Modbus cables.
Cable shields must always be electrically connected to the earthed product enclosure.
Use the internal, factory-fitted cable clamps to ensure proper shield connection.
Never convey mains voltage, motor connections and control signals in the same cable.
The +24 VDC from the OJ-DV is not intended to be used as power supply for third party products.
If the +24 is used for power supply to third party products, the product might not fulfill the EMC
regulations.
Note
13.3 Short-circuit protection – Power supply
Short-circuit protection for the supply side of OJ-DV is not provided together with the product.
Correct short-circuit protection at the power supply input side on the OJ-DV must always be used
in accordance with local and international regulations.
Short-circuit protection equipment must as a minimum have a tripping curve “C” conforming to
IEC 60898-1.
Short-circuit protection is supplied by the installer.
Warning
13.4 PERSONAL PROTECTION - USE OF RCDs (TT-system), DIRECT CURRENT (AC/DC) RISK
This product can cause a DC current in the ground protective conductor in the event of a ground
fault.
If the 3 phases to the OJ-DV are not switched in at exactly the same time, then there will be a
generated current in the earthing/ground conductor during the switching time until all 3 phases are
connected.
Take notice of the following precautions:
If a residual current device (RCD) is used for extra personal protection, use only an RCD of Type
B on the supply side of this product (B type, for alternating and/or pulsating current with DC
components and continuous fault current).
RCDs of type B must comply with all provisions of IEC 61008/9
Protective earthing of the OJ-DV in combination with the use of RCDs must always be performed
in accordance with the relevant local and international requirements, laws and regulations
Failure to follow these precautions can lead to severe or fatal injuries to persons and animals.

Questions and Answers: