EasyManuals Logo

Oldham 700 TP Series User Manual

Oldham 700 TP Series
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
OLCT 700/710 TP
OLCT 700/710 TP Instruction Manual Rev. C.1 Page 33 of 45
Nuisance Alarms
Check condulet for accumulated water and abnormal corrosion on terminal blocks.
If nuisance alarms are happening at night, suspect condensation in condulet. Add or replace
Oldham’s Condensation Prevention Packet PN DET-960-202200-000.
Investigate the presence of other target gases that are causing cross-interference signals.
Determine if cause is RFI induced.
Processor and/or Memory Faults
Recycle power in attempt to clear problem
Restore Factory Defaults - This will clear the processor’s memory and may correct
problem.Remember to re-enter all customer settings for range and cal gas level after Restore
Factory Defaults.
If problem persists, replace the Intelligent Transmitter Module.
Unreadable Display
If due to excessive sunlight, install a sunshade to reduce glare.
Nothing Displayed Transmitter not Responding
Verify condulet has no accumulated water or abnormal corrosion.
Verify required DC power is applied to correct terminals.
Swap with a known-good ITM to determine if ITM is faulty.
Faulty 4-20mA Output
If Detector has a normal reading with no Faults displayed, and the 4-20 mA signal output is 0mA.
Check that wiring is properly connected at terminal blocks and through to controller inputs. The 4-
20mA output loop must be closed to avoid a Loop Fault. If the 4-20mA output is not being used
the green wire from the detector must be connected to the (-) terminal on the Transient Protection
Module to ensure that it does not create a 4-20mA Fault (section 0).
Perform a “Signal Output Check” sequence via Section 3.5.7 and verify 4-20mA output with
Current Meter.
Swap with new ITM to determine if the ITM’s 4-20mA output circuit is faulty.
If the 4-20mA current loop is still out of tolerance, contact Oldham’s Technical Support at
support@oldhamgas.com.
No Communication - RS-485 Modbus™
If detector has a normal reading with no Faults displayed and the Modbus™ is not communicating.
Verify that the correct (and non-duplicated) serial address is entered (per Section 0).
Check that the wiring is properly connected at terminal blocks, and the serial loop is wired
correctly.
Perform a “Signal Output Check” per Section 3.5.7 and troubleshoot wiring.
Consider adding a Modbus™ repeater if the distance from the nearest distribution drop is
excessive.
Swap with new ITM to determine if the ITM’s serial output circuit is faulty.
Refer to Oldham’s “Guide to Proper Modbus™ Communications” Application Note.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Oldham 700 TP Series and is the answer not in the manual?

Oldham 700 TP Series Specifications

General IconGeneral
BrandOldham
Model700 TP Series
CategoryAccessories
LanguageEnglish