EasyManua.ls Logo

Olimpia splendid PHENIX E - Page 74

Olimpia splendid PHENIX E
312 pages
Go to English
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
min.
300mm
min.
300mm
min.
600mm
min.
300mm
min.
2000mm
min. 600mm
A
B
C
D
C
F
A
E
X3
IN
IN
OUT
286
mm
452mm
X4
ENGLISH
EN - 18
2.6.1 - Condensation drainage in heat pump operation
• During operation in heating mode, condensate is produced in the outdoor unit due to defrosting, which
must be able to run-off freely to prevent stagnation.
• Whenpositionedonaatsurface,adrainingchannelmustbecreatedaroundtheunitthatgoesdirectly
intotherainwatercollectionwellofthewaternetwork(gure15).
• In the case of installation on a balcony or terrace, it must be possible to position a recipient under the
unit,possiblyingalvanisedsheetorstainlesssteel(preferable),withdrainpipethatowsdirectlyintothe
gutter.
• Anotheroption(gure16)istopositionthegasket(6)onthetting(5)andtheninsertthelatterintothe
holemadeonthebottomoftheoutdoorunitandturnitby90°toxitsecurely.
• Connectarubberhose(notsupplied)tothetting(6)ifwaterisdrainedfromtheoutdoorunitinheating
mode.
2.6.2 - Outdoor unit assembly
Proceed as follows (as described in the previous paragraph), once the ideal position for installation of the
outdoorunithasbeenidentied:
a. Positiontheunitonthesupportbase,respectingthedrillingdistancesindicatedinthetableingureX4.
b. Screw any clamping nuts, without tightening completely.
c. Using a spirit level, check the unit is level; if necessary, adjust the support feet.
d. Tighten any clamping nuts correctly.
IN = air inlet - OUT = air outlet
e. If the outdoor unit is higher than the indoor units, to prevent rain entering, a downward bow must be made
along the connection pipe (siphon) before the connection pipe enters the wall. This is to guarantee that
the lowest point of the connection pipe is outdoors.
p. Make sure that there is the minimum space around the outdoor unit necessary to guarantee correct
operationandthecleaningandmaintenanceinterventions,asindicatedingureX3.

Table of Contents

Related product manuals