ISS0011R10_A_EN.doc
PARAMETERS TABLE
Mnemonic Value Description Expected range
Scale_m
18°C
Minimum scale
10…32°C
Tset
22°C
Setpoint
10…38°C
Hy
Hysteresis
0.5…10°K
Adj
Ambient probe input calibration
-
15…+15°K
tmin
22°C
Anti
-
ice
formation temperature
10…30°C
tmax
32°C
Anti explosion tempera
ture
25…50°C
Tp_on
20 min.
Anti
-
ice
programme ON time
3…60 min.
Tp_off
3 min.
Anti
-
ice
programme OFF time
3…15 min.
Rest_time
180 sec.
Compressor
start
-
up
delay
0…255 sec.
Tdiag
20 min.
Diagnostic time with compressor ON
0…60 min
Step
Setpoint adjustment step
0.5…5°K
Tsf
250h
Filter Dirty alarm activation time
250
-
1000
2. STANDBY MODE
Selectable by pressing the corresponding key on the remote or locally on the display-unit (in the latter case
the key performs this function only when the machine is working and there are no ongoing malfunctions).
When the corresponding LED turns on (DL1) it means this mode is active and all the outputs are off. In this
condition, by pressing the STANDBY key again on the remote or the key on the display, all the previously
selected functions are reset (operating mode, set-point, fan speed, activation timer, etc.) and the timed settings
for the various programmes (except for compressor rest time) are reinitialized. Machine functioning mode
will be that corresponding to the activation mode. Triggering of the ‘Probe KO’ malfunction is enabled in this
status.
3. FAN MODE
Selectable only with the remote control. The fan is always powered in this mode and its speed can be selected
at any time with the key on the remote control. All the malfunctions that can be expected for the machine are
enabled in this status.