BS-634, BS-636
4 and 6 zone Fire Detection Panels
921636000_09_023
Thank you for purchasing this product of Olympia Electronics. A European manufacturer.
GENERAL
The family of fire detection panels consist of 2 types( 4 and 6 zone) with identical operation and indications. The panels have
2 independent siren outputs, Alarm relay, Programmable output for telephone operators and a relay per zone . The required
battery for the panels is the type Α-986 (12V/7Ah). All functions and indications are according to European Norms ΕΝ 54-2
and EN 54-4.
Top cover
retaining screws
Control Keyboard and
indication leds
Mounting holes
Battery compartment
Α-986
MODE selection
microswitch
Relay per zone
connection terminal s
Zone connection termi nal
General output connec tion (Sirens,
relay alarm,24V)
P
+A
_
A
Operation adjustmen t
of zone relay
Mains voltage connect ion
terminal block (220-2 40V AC)
Figure 1. Schematic diagram of the panel
Mounting hole
Extra earth
terminals
Page 1 from 9
High Quality European based Manufacturers
Question and Answer IconNeed help?

Do you have a question about the olympia electronics BS-634 and is the answer not in the manual?

olympia electronics BS-634 Specifications

General IconGeneral
Brandolympia electronics
ModelBS-634
CategoryMeasuring Instruments
LanguageEnglish

Summary

Indication LED Description

Panel Indicator LEDs

Description of General, Zone Alarm, Fault/Disable, Power, CPU, and Siren LEDs.

Control Keyboard Operation

Access Levels 1 & 2 Functions

Functions for user access levels 1 (no code) and 2 (code '34') for panel operation.

Advanced Control Features

Connections and Wiring

Installation Guidelines

Initial Installation and Testing

Installation Procedure

Special configuration for initial installation and troubleshooting using MODE switch 1.

Walk-Testing Procedure

Procedure to enter walk-test mode and test zone operation using MODE switch 1.

Technical Specifications

Related product manuals