9. FAN & MOTOR DATA
9.1 PSC Motor Data
Note: Please call customer service for external static pressure requirements exceeding 0.5” w.g.
150 200
LOW 285 230 210 195 160 - -
MED 320 270 250 225 200 160 -
HIGH 430 355 340 315 280 240 185
210 350
LOW 275 235 220 - - - -
MED 310 275 250 230 - - -
HIGH 405 370 350 315 280 235 -
270 460
LOW 340 300 275 - - - -
MED 410 370 350 338 315 - -
HIGH 600 550 520 500 380 310 -
370 530
LOW 560 510 475 450 - - -
MED 645 585 550 505 460 415 -
HIGH 765 715 670 630 585 530 455
410 630
LOW 560 510 475 450 - - -
MED 645 585 550 505 460 415 -
HIGH 765 715 670 630 585 530 455
270 820
LOW 785 735 700 655 615 570 -
MED 855 790 750 710 670 615 -
HIGH 895 840 790 745 710 645 600
640 1010
LOW 895 855 790 745 670 - -
MED 1045 970 925 855 785 710 -
HIGH 1155 1075 1010 935 845 775 670
740 1200
LOW 1155 1080 1015 950 875 790 -
MED 1170 1095 1025 970 890 800 -
HIGH 1225 1150 1080 1000 935 850 760
Note: All airflow ratings are taken at lowest voltage rating of dual rating (ie. 208 volt).
Airflow ratings include resistance of dry coil, Return Air panel and clean MERV10 air filters.