Parameter
No.
Function name Monitor or Data Range
Default
data
Setting
during
RUN
Unit Page
H07
Acceleration/Decelera-
tion Pattern Selection
0: Disable (Linear accelera-
tion/deceleration)
1: S-curve acceleration/decel-
eration (Weak)
2: S-curve acceleration/decel-
eration (Arbitrary: According to
H057 to H060)
3: Curve acceleration/deceler-
ation
0
Availa-
ble
-
page
5-40
H08
Reverse Rotation Pre-
vention Function
0: Disable
1: Reverse rotation inhibited
2: Forward rotation inhibited
0 - -
page
7-117
H09
Starting Mode Auto
Search Function Se-
lection
0: Disable
1: Enable only at restart after
momentary power failure
2: Enable at normal start and
restart after momentary power
failure
0 - -
page
7-49
H11 Stop Selection
0: Normal deceleration
1: Free run stop
0
Availa-
ble
-
page
5-47
H12
Instantaneous Over-
current Limiting Func-
tion Selection
0: Disable
1: Enable
1
Availa-
ble
-
page
7-87
H13
Power Interruption Re-
start Wait Time
0.1 to 100.0 s
0.5
Availa-
ble
s
page
7-49
H14
Deceleration Setting
During Current Limit
for Restart Mode after
Power Interruption
0.00: Selected deceleration
time
0.01 to 100.00 Hz/s
999: According to current limit-
er
32767
Availa-
ble
Hz/s
page
7-49
4 Parameter List
4-117
M1 Series Standard Type User's Manual (I669)
4-2 List of Parameters by Group
4
4-2-5 Parameter H (High Level Functions)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron 3G3M1-A Series and is the answer not in the manual?

Omron 3G3M1-A Series Specifications

General IconGeneral
BrandOmron
Model3G3M1-A Series
CategoryInverter
LanguageEnglish

Related product manuals