91
Error Codes and Monitoring Section 7-2
Using the following system, let’s assume errors have occurred in words 230
and 231 (word settings 30 and 31) and that words 230 and 231 have been
allocated to Remote Terminals.
Remote
T
erminal
IR
7
IR 6
IR 5
IR 4
Master #0
IR 2
IR 1
Word
setting:
0
Allocation: 200
Master #1
IR 13
IR 12
IR 11
IR 10
Slave #0
IR 54
IR 53
IR 52
IR 5
IR 50
Expansion
I/O Rack
Remote T
erminal
W
ord setting:
30
Allocation: 230
Remote T
erminal
W
ord setting:
31
Allocation: 231
C200H PC
Slave Rack
I/O
connecting
cable
Word 251 contains the following data.
Bit
no.
IR 251
OOO1 OOOOO 01OO1 OO
3008
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Monitoring word 59 with the Programming Console produces the following
display.
Indicates Remote I/O error.
Indicates word setting of 30 (allocated word 230).
Indicates Master #0.
Locating Errors: C200H
Systems