CONTINUE and STOP Mode Operation Section 7-4
7-4 CONTINUE and STOP Mode Operation
The following tables can be compared and contrasted to understand differ-
ences between CONTINUE and STOP mode operation. These modes are
set on Masters. Refer to
Subsection 4-1
for setting details.
The following configuration and table will be used to show LED indications
when power to Slave #0 is interrupted in CONTINUE mode. Refer to
Section
2
for details on indicator operation.
C500 CPU Rack
C500 Master
C500 Slave
Slave #0
C500 Slaves
Slave #1 T
erminator
Condition C500 LEDs LEDs on Master LEDs on
Slave #0
LEDs on
Slave #1
POWER RUN ERROR ALARM OUT IN TR/
ERR
TEST
OK
END
RS
CHECK
LINE
ERR
TR/
ERR
ERR TR/
ERR
ERR
Normal
operation
lit lit not
lit
not lit not lit
flash
not lit not lit
not
lit
flash
not lit
flash
not lit
Power
in
-
terruption
to Slave
#0
lit lit
not lit
lit
not lit
lit
not lit not lit
not
lit
not
lit
not lit
flash
not lit
Remote I/O error occurs; operation continues.
Word 59 contains “#B008.”
Transmission error occurs;
transmission to Slave #1 con-
tinues.
Power inter-
rupted.
Normal op-
eration.
Power re-
stored to
Slave #0
lit lit
not lit
lit
not lit
flash
not lit not lit
not
lit
flash
not lit
flash
not lit
1. All ALARM LEDs turned off by performing
recovery operation from Programming
Console.
2. Remote I/O Error flag cleared by turning
Error Check flag ON, then OFF again.
Normal operation Normal operation
Operations in CONTINUE
Mode