Remote Terminal Section 4-2
53
Pins 1 through 3: Unit Number
Unit number* Pin 1 2 3
0 OFF OFF OFF
1 OFF OFF ON
2 OFF ON OFF
3 OFF ON ON
4 ON OFF OFF
5 ON OFF ON
6 ON ON OFF
7 ON ON ON
*Unit numbers 0 and 1 can be set for C120 and C500 Systems; unit numbers
0 through 4 for C200H Systems; and 0 through 7 for C1000H and C2000H
Systems.
Pin 4: Type of Master
ON Master other than C200H
OFF C200H Master
Pin 5: Output HOLD/STOP Mode
ON HOLD mode, i.e, all output words retain status in for transmission errors.
OFF STOP mode, i.e., all output words set to OFF for transmission errors.
Pin 6:
Pin 6 should always be set to OFF.
4-2 Remote
T
erminal
The procedure for setting the switches in the Remote Interface is exactly the
same as in the Remote Terminals. Only a Remote Interface is shown below.