95
CONTINUE and STOP Mode Operation Section 7-4
The following configuration and table will be used to show LED indications
when power to Slave #0 is interrupted in STOP mode Refer to
Section 2
for
indicator details.
C500
Master
C500 Slave
Slave #0
C500 Slaves
Slave #1 T
erminator
C500 CPU Rack
Condition C500 LEDs LEDs on Master LEDs on
Slave #0
LEDs on
Slave #1
POWER RUN ERROR ALARM OUT IN TR/
ERR
TEST
OK
END
RS
CHECK
LINE
ERR
TR/
ERR
ERR TR/
ERR
ERR
Normal
operation
lit lit not
lit
not lit not lit
flash
not lit not lit
not
lit
flash
not lit
flash
not lit
Power
in
-
terruption
to Slave
#0
lit lit
not lit
lit
not lit
lit
not lit not lit
not
lit
not
lit
not lit
lit
not lit
Remote I/O error occurs; operation continues.
Word 59 contains “#B008.”
Transmission error occurs;
transmission to both Slaves
stopped.
Power inter-
rupted.
Transmis-
sion error
Power re-
stored to
Slave #0
lit lit
not lit
lit
not lit
lit
not lit not lit
not
lit
lit
not lit
lit
not lit
Remote I/O error. Transmission error; no trans-
mission to Slaves
Not
functioning.
Transmis-
sion error;
not func-
tioning
Operations in STOP Mode