96
CONTINUE and STOP Mode Operation Section 7-4
(Restarting Remote I/O System)
Condition C500 LEDs LEDs on Master LEDs on
Slave #0
LEDs on
Slave #1
POWER RUN ERROR ALARM OUT IN TR/
ERR
TEST
OK
END
RS
CHECK
LINE
ERR
TR/
ERR
ERR TR/
ERR
ERR
I/O
table
created
(PRO-
GRAM
mode).
lit lit
not lit not lit not lit
flash
not lit not lit
not
lit
flash
not lit
flash
not lit
1. Create I/O table in PROGRAM mode and
then set into RUN or MONITOR mode.
2. Error flag is cleared when I/O table is
created.
1. Transmissions with Slave
started when I/O table is
created.
2. PC operation begins when
RUN or MONITOR mode
is entered.
Transmis-
sions
started
when I/O
table is
created.
Transmis-
sions
started
when I/O
table is
created. All
outputs are
turned of
f if
the Slave is
set in
HOLD
mode.
TEST
switch
pressed
(any
mode).
lit lit
not lit
lit
not lit
flash
not lit not lit
not
lit
flash
not lit
flash
not lit
1. All ALARM LEDs turned off by performing
recovery operation from Programming
Console.
2. Remote I/O error flag cleared by turning
error check flag OFF, ON, then OFF
again.
1. Transmissions with Slave
started when TEST switch
is pressed.
2. If TEST switch is pressed
in PROGRAM mode,
transmissions will start
when the TEST switch is
pressed, but operation
(i.e., refreshing Slave I/O)
begins when RUN or
MONITOR mode is en-
tered.
Transmissions started
when TEST switch is
pressed.
(Restarting Remote I/O System, Continued)
Condition C500 LEDs LEDs on Master LEDs on
Slave #0
LEDs on
Slave #1
POWER RUN ERROR ALARM OUT IN TR/
ERR
TEST
OK
END
RS
CHECK
LINE
ERR
TR/
ERR
ERR TR/
ERR
ERR
Power
to
system
turned
back on.
lit lit
not lit not lit not lit
flash
not lit not lit
not
lit
flash
not lit
flash
not lit
Normal
operation
Normal operation Normal operation