28
Unit Numbers and I/O Word Allocation Section 3-2
Set the word multipliers in a C1000H and C2000H System using the Pro-
gramming Console as shown below. Before setting word multipliers, set the
mode selector to PROGRAM. Word multipliers must be assigned only to the
Masters to which Remote Terminals are connected. Displays for word multi-
pliers are not displayed for Masters to which only Slaves are connected.
Initial clear all
Register
I/O table
Continue registering word multipliers
by entering them with the WRITE key
.
Automatically checks I/O table.
The CPU Unit takes about 2 s
here.
Indicates word multiplier not yet speci
-
fied.
Once the word has been specified
and entered with the WRITE key
,
proceed to the next master
.
When a word has already been registered, it
will be displayed. Press the WRITE key to
continue without changing it, or input a new
multiplier before the WRITE key to change it.
Appears when all word multipliers have
been registered, completing the operation.
Setting Word Multipliers