Output Unit
(1) If different terminal block or connector is used, you have to change the wiring.
(2) If the number of circuit is different (increased), wire and connect the terminals and each common terminals.
(3) If the output specification is not same, check if there is no problem in operation.
(4) The relay lifetime might change depending on the usage, when the used relay is different. Refer to the
Appendix F Restrictions in Using C200H Special I/O Units in the CS1G/H-CPU**H/CS1G/H-CPU**-EV1 CS
SERIES CPU UNITS OPERATIAN MANUAL (Cat. No. W339) for details of the Output Units.
(5) If the current consumption is different, check if enough power supply capacity is provided
(6) If the voltage and current consumption of external power supply is different, check if enough power supply
capacity is provided.
(7) C200H-series Units can be used with CS1-series CPU Unit.
(8) Refer to related manuals for details, even if functions of C200H-series are supported by CS1-series Units,
since a part of specifications may differ.
<Relay Output Units>
C200H-series Unit Corresponding CS-series Unit Description Difference
C200H-OC223 CS1W-OC201
250VAC/24VDC, 2A, Terminal
block, 5 outputs
(independent contacts)
250 VAC or 120 VDC,
2 A max., terminal block, 8
outputs (Independent contacts)
Relay Output Units with
terminal block for 5 outputs
(independent contacts).
Replace this unit with a Relay
Output Unit with 8 outputs
(independent contacts).
1) Terminal block
2) Output points (independent contacts 5
points -> 8 points)
3) Output circuit specification
ON/OFF response time(10ms->15ms)
Used relay
4) Internal current consumption
(5VDC:10mA->100mA,
26VDC:46mA->48mA)
C200H-OC224 CS1W-OC201
250VAC/24VDC, 2A, Terminal
block, 8 outputs (independent
contacts)
250 VAC or 120 VDC,
2 A max., terminal block, 8
outputs (Independent contacts)
Relay Output Units with
terminal block for 8 outputs
(independent contacts).
1) Terminal block
2) Output circuit specification
ON/OFF response time(10ms->15ms)
Used relay
3) Internal current consumption
(5VDC:10mA->100mA,
26VDC:75mA->48mA)
C200H-OC224V, OC224N CS1W-OC201
250VAC/24VDC, 2A, Terminal
block, 8 outputs (independent
contacts)
250 VAC or 120 VDC,
2 A max. , terminal block, 8
outputs (Independent contacts)
Relay Output Units with
terminal block for 8 outputs
(independent contacts).
1) Terminal block
2) Output circuit specification
Used relay
3) Internal current consumption
(5VDC:10mA->100mA, 26VDC:90mA->
48mA)
C200H-OC221 CS1W-OC211
250VAC/24VDC, 2A, Terminal
block, 8 outputs
250 VAC or 120 VDC,
2 A max., terminal block,
16 outputs
Relay Output Units with
terminal block for 8 outputs.
Replace this unit with a Relay
Output Unit with 16 outputs.
1) Terminal block
2) Output points(8 -> 16 points)
3) Output circuit specification
ON/OFF response time(10ms->15ms)
Used relay
4) Internal current consumption (DC5V
10mA->100mA, DC26V75mA->96mA)
C200H-OC222 CS1W-OC211
250VAC/24VDC, 2A, Terminal
block, 12 outputs
250 VAC or 120 VDC,
2 A max., terminal block,
16 outputs
Relay Output Units with
terminal block for 12 outputs.
Replace this unit with a Relay
Output Unit with 16 outputs.
1) Terminal block
2) Output points(12 -> 16 points)
3) Number of circuit(12 points/common x1
circuit -> 8 points/common x2 circuits)
4) Output circuit specification
ON/OFF response time(10ms->15ms)
Used relay
5) Internal current consumption
(5VDC:10mA->100mA,
26VDC:75mA->96mA)
C200H-OC222V, OC222N CS1W-OC211
250 VAC/24VDC,
2A, Terminal block, 12
outputs
250 VAC or 120 VDC,
2 A max.
16 outputs
Relay Output Units with
terminal block for 12 outputs.
Replace this unit with a Relay
Output Unit with 16 outputs.
1) Terminal block
2) Output points (12 -> 16 points)
3) Number of circuit (12 points/common x1
circuit ->8 points/common x2 circuits)
4) Output circuit specification
Used relay
5) Internal current consumption
(5VDC:10mA->100mA,
26VDC:90mA->96mA)
󲨩󲨯

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron C200H Series and is the answer not in the manual?

Omron C200H Series Specifications

General IconGeneral
Humidity10% to 90% RH (non-condensing)
Programming LanguageLadder Diagram, Instruction List
Communication PortsRS-232C, RS-422/485
Operating Temperature0 to 55°C (32 to 131°F)
MountingDIN rail
TypeProgrammable Logic Controller (PLC)
Power Supply100 to 240 VAC, 24 VDC

Related product manuals