EasyManua.ls Logo

Omron E5CK-AA1-302 - Sensor Input Wiring Diagrams; E5 AK, E5 EK, and E5 CK Sensor Input Wiring

Omron E5CK-AA1-302
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E5AK/E5CK/E5EK
E5AK/E5CK/E5EK
123
SENSOR INPUT WIRING
E5AK
Connect the sensor input to terminal numbers 11 to 14 and 33 as follows according to the input type.
E5EK
Connect the sensor input to terminal numbers 11 to 14 and 23 as follows according to the input type.
E5CK
Connect the sensor input to terminal numbers 6 to 8 as indicated here, according to the input type.
8
7
6
8
7
6
8
7
6
8
7
6
-
+
-
+
-
+
VmA
TC PT V I
Thermocouple Platinum resistance
thermometer (RTD)
Voltage input Current input
Input type
Internal jumper
setting
5
4
3
2
1
10
9
13 14
11 12
8
7
6
Match the inputs with the internal jumper settings for each input type. For thermocouple or platinum resistance thermometer inputs, set
the internal jumper to a common position (TC/PT) as the temperature input.