140
Advanced Function Setting Level Section 5-7
This parameter sets the key pressing time required to move to the protect
level from the operation level or the adjustment level.
Related Parameters
Operation/adjustment protect, initial setting/communications protect, setting
change protect (protect level): Page 96
When this parameter is set to ON, alarm 1 output turns ON for input
e
rrors.
The alarm 1 operation indicator will not light.
Note For details on input errors, refer to Error Displays on page 156.
The alarm 1 output is an OR output of alarm 1, HB alarm burnout/HS
alarm, and input error.
Output is turned OFF when switching to the initial setting level, communi-
cations setting level, or advanced function setting level.
Specifies whether cold junction compensation is to be performed inter-
nally by the Controller or to be performed externally when the input type
setting is to between 5 and 22.
The cold junction compensation external setting is enabled when the tem-
perature difference is measured using two thermocouples or two ES1B
Sensors.
Related Parameter
Input type (initial setting level): Page 119
prlt Move to Protect Level Time
Setting range Unit Default
1 to 30 Second 3
Function
Setting
See
See
sero Input Error Output
Alarm 1 must be assigned.
Setting range Default
on: Enabled, off: Disabled off
Function
Setting
cjc Cold Junction Compensation Method
Input type must be thermocouple or
infrared temperature sensor
Setting range Default
on: Internally, off: Externally on
Function
Setting
See
See