25
G9SX-GS
Specifications
Ratings
Power Input
* Power consumption of loads not included.
Inputs
* Provide a current equal to or higher than that of the minimum applicable load of the connected input control device.
Outputs
*1. While safety outputs are in the ON state, the following signal sequence is output continuously for diagnosis.
When using the safety outputs as input signals to control devices (i.e. Programmable Controllers), consider the OFF pulse shown below.
*2. The following derating is required when Units are mounted side-by-side.
G9SX-GS226-T15-@: 0.4 A max. load current/output
Expansion Unit
Item Model G9SX-GS226-T15-@ G9SX-EX-@
Rated supply voltage 24 VDC
Operating voltage range −15% to 10% of rated supply voltage
Rated power consumption * 5 W max. 2 W max.
Item Model G9SX-GS226-T15-@
Safety inputs
Operating voltage: 20.4 VDC to 26.4 VDC, Internal impedance:
Approx. 2.8 kΩ *
Mode selector input
Feedback/reset input
Item Model G9SX-GS226-T15-@
Instantaneous safety outputs *1
OFF-delayed safety outputs *1
P channel MOS-FET outputs
Load current: 0.8 A DC max./output *2
Auxiliary outputs
(for input, output, and error monitoring)
PNP transistor outputs
Load current: 0.8 A DC max./output *2
External indicator outputs
P channel MOS-FET outputs
Connectable indicators
• Incandescent lamp: 24 VDC, 3 to 7 W
• LED lamp: 10 to 300 mA DC/output
Item Model G9SX-EX-@
Rated load 250 VAC, 3 A / 30 VDC, 3 A (resistive load)
Rated carry current 3 A
Maximum switching voltage 250 VAC, 125 VDC
ON
OFF
360 μs max.
Approx. 100 ms