31
G9SX-GS
Setting Procedure
1.Switching Function
Auto or manual switching is set by using the Switching Function
setting switch on the bottom of the G9SX-GS@. Set the switch to Auto
for auto switching and Manual for manual switching.
For manual switching, connect the mode selector as shown in the
following table.
2.Reset Mode
Set the reset mode using feedback/reset input terminals T31, T32,
and T33.
Auto reset mode is selected when terminal T32 is shorted to 24 V and
manual reset mode is selected when terminal T33 is shorted to 24 V.
3.Cross Fault Detection
When connecting a Door Switch or other safety input device, you can use Y1 or Y2 to switch the cross fault detection setting.
When Y1 is open, short-circuit failures are detected between safety inputs T11-T12 and T21-T22. When Y2 is open, short-circuit failures are
detected between safety inputs T61-T62 and T71-T72. When a cross fault is detected, the following will occur.
1. The safety outputs and logical AND output will be locked out.
2. The LED error indicator will light.
3. The error output (auxiliary output) will turn ON.
When a safety sensor, such as a Safety Light Curtain, is connected to safety input A, connect Y1 to 24 V. When a safety sensor is connected to
safety input B, connect Y2 to 24 V. If they are not connected to 24 V, the G9SX-GS@ will detect an error.
Switching
function
Mode selector connection
Auto switching
Manual switching
M1 ON, M2 OFF: Normal operating mode
M1 OFF, M2 ON: Maintenance mode
M2M1
OpenOpen
M2M1
+24 V
Maintenance
mode
Normal
operating
mode
+24
V +24 V
Auto reset mode
KM1
KM2
KM3
KM4
KM5
KM1
KM2 Reset
switch
KM3
KM4
KM5
T33 T32 T31 T33 T32 T31
Manual reset mode
Cross fault
detection
Equivalent safety
category
Safety input A Safety input B
OFF
Using 1 safety input
channel
Using 2 safety input
channels
ON
Y1
T22 T21 T12 T11
+24 V
+24 V
S1
Y2
T72 T71 T62 T61
+24 V
+24
S1
Y1
T22 T21 T12 T11
+24 V
+24 V +24 V
S1 S1
Y2
T72 T71 T62 T61
+24 V
+24
+24
S1 S1
Y1
T22 T21 T12 T11
Open
S1 S1
S1 S1
Y2
T72 T71 T62 T61
Open