8
G9SX
Logical AND Connection
Note: See Logical AND Connection Combinations below for details.
*1. The number of G9SX-EX401-@ Expansion Units or G9SX-EX041-T-@ Expansion Units (OFF-delayed Model) not included.
*2. G9SX-EX401-@ Expansion Units and G9SX-EX041-T-@ Expansion Units (OFF-delayed Model) can be mixed.
Logical AND Connection Combinations
1. One logical AND connection output from an Advanced Unit
G9SX-AD can be logical AND connected to up to four Advanced
Units.
2. Two logical AND outputs from a Basic Unit G9SX-BC can be
logical AND connected to up to eight Advanced Units.
3. Two logical AND outputs from an Advanced Unit G9SX-ADA can
be logical AND connected to up to eight Advanced Units.
4. Any Advanced Unit with logical AND input can be logical AND
connected to Advanced Units on up to five tiers.
5. Two logical AND connection outputs, each from different
Advanced/Basic Units, can be logical AND connected to a single
G9SX-ADA Unit.
6. The largest possible system configuration contains a total of 20
Advanced and Basic Units. In this configuration, each Advanced
Unit can have up to five Expansion Units.
Item Model G9SX-AD322-@/ADA222-@ G9SX-BC202-@ G9SX-EX-@
Number of Units connected per logical AND
output
4 Units max. ---
Total number of Units connected by logical
AND *1
20 Units max. ---
Number of Units connected in series by
logical AND
5 Units max. ---
Max. number of Expansion Units connected
*2
--- 5 Units max.
Maximum cable length for logical AND input 100 m max./output ---
G9SX-AD
G9SX-AD G9SX-AD G9SX-AD
100 m max.
G9SX-AD
G9SX-BC
G9SX-AD
G9SX-AD G9SX-AD G9SX-AD G9SX-AD
G9SX-AD G9SX-AD G9SX-AD
100 m max.
100 m max.
G9SX-AD
G9SX-AD G9SX-AD G9SX-AD G9SX-AD
G9SX-ADA
G9SX-AD G9SX-AD G9SX-AD
100 m max.
100 m max.
G9SX-BC or
G9SX-AD or
G9SX-ADA
G9SX-AD
G9SX-AD
G9SX-AD
G9SX-AD
100 m max.
100 m max.
100 m max.
100 m max.
G9SX-BC G9SX-BC
G9SX-ADA
100 m max. 100 m max.
Number of Units connected
per logical AND output:
4 Units max.
Total number of Units
connected by logical AND:
20 Units max.
Number of Units connected
in series by logical AND:
5 Units max.
Note 1: Basic Unit = G9SX-BC
Advanced Unit = G9SX-AD or G9SX-ADA
Note 2: The G9SX-AD322-T-@ has only one logical AND
output.
Advanced Unit
or Basic Unit
Advanced UnitAdvanced Unit Advanced Unit
Advanced Unit
Advanced Unit Advanced Unit Advanced Unit
Advanced Unit
Advanced Unit Advanced Unit Advanced Unit
Advanced Unit Advanced Unit Advanced Unit
Advanced Unit
Advanced Unit Advanced Unit Advanced Unit
Advanced Unit

Other manuals for Omron G9SX Series

Related product manuals