Input Connections
Open Collector Output Voltage Output
12 VDC
17653
--
7986
PC or sensor
0 V Output
12 VDC
PC or sensor
0 V Output
AC models
DC models
17653
--
7986
AC models
DC models
Gate input
Start input
Reset input
12 VDC output
Gate input
Start input
Reset input
12 VDC output
0V
0V
Contact input
7653
7986
AC models
DC models
Gate input
Start input
Reset input
Start, Reset, and Gate Input Specification
ON impedance: 500
$
max. (the leakage current is 5 to 20 mA when the impedance is 0
$
.)
ON residual voltage: 2 V max.
OFF impedance: 100 k
$
min.
Maximum applicable voltage: 30 VDC max.
Two-wire Sensor
7653
7986
Sensor
0V
AC models
DC models
Gate input
Start input
Reset input
0V
Applicable Two-wire Sensor
Leakage current: 1.5 mA max.
Switching capacity: 5 mA min.
Residual voltage: 3 V max.
Operating voltage: 10 VDC
Note: When connecting a two-wire sensor to a DC models, sup-
ply 24 VDC (21.6 to 26.4 VDC) to the timer.
Key Protection Input
43
106
AC models
DC models
Open collector
or
contact
0V
Key protection
input
Key Protection Input
ON impedance: 1 k
$
max.
(the leakage current is approx. 1 mA when the impedance is 0
$
.)
ON residual voltage: 0.5 V max.
OFF impedance: 100 k
$
min.
Maximum applicable voltage: 30 VDC max.
Note: The used contact should switch 1 mA at 5 V.
Precautions
Power Supplies
When turning the power ON and OFF, input signal reception is pos-
sible, unstable, or impossible as shown in the diagram below.
Power
supply
Input Impossible
Unstable
Possible ImpossibleUnstable
160 ms
0to90ms
DC: 5 ms
AC: 10 ms
0to500ms
ON
OFF
Apply the power supply voltage through a relay or switch in such a
way that the voltage reaches a fixed value immediately.
Turnthe power ON and OFF with relay with a rated capacity of 10 A
minimum to prevent contact deterioration due to inrush current
caused by turning the power ON and OFF.

Other manuals for Omron H3CR-A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron H3CR-A and is the answer not in the manual?

Omron H3CR-A Specifications

General IconGeneral
Time Range0.05 seconds to 300 hours
Output TypeRelay
Mounting TypeDIN Rail
Operating Temperature-10°C to 55°C
Contact FormSPDT
Number of Pins8
Contact Rating5A at 250VAC
Storage Temperature-25°C to 65°C
TypeSolid State Timer
Dimensions48 mm x 48 mm
Operating ModeON-delay, OFF-delay, Interval, One-shot
Operating Voltage24V DC, 100-240V AC