B-70 Solid-state Star-delta Timer H3DE-G
Specifications
General
Note: Can be mounted to 35-mm DIN track with a plate thickness of 1 to 2.5 mm.
Time Ranges
Ratings
Note: DC ripple rate: 20% max.
Item H3DE-G
Operating mode Star-delta operation
Operating/Reset method Time-limit operation/Self-reset
Terminal block
Clamps two 2.5 mm
2
max. bar terminals without sleeves
Terminal screw tightening torque 0.98 N·m max. {approx. 10 kgf·cm max.}
Output type (Star operation circuit) Relay: SPDT
(Delta operation circuit) Relay: SPDT
Mounting method DIN track mounting (see note)
Attachment Nameplate
Approved standards UL508, CSA 22.2 No.14
Conforms to EN61812-1, IEC60664-1 4 kV/2, VDE0106/P100
Output category according to IEC60947-5-1 (AC-13; 250 V 5A/AC-15; 250 V 3 A/DC-13; 30 V 0.1 A)
Time scale display Star operation time ranges
x 1 1 to 12 s
x 10 10 to 120 s
Star-delta transfer time Programmable at 0.05 s, 0.1 s, 0.25 s or 0.5 s
Rated supply voltage (see note) 24 to 230 VAC/VDC (50/60 Hz)
Operating voltage range 85% to 110% of rated supply voltage
Power reset Minimum power-off time: 0.5 s
Reset voltage 24 VAC/DC max.
Power consumption AC: Approx. 3 VA (1.8 W) at 230 VAC
DC: Approx. 0.8 W at 24 VDC
Control output Contact output: 5 A at 250 VAC with resistive load (cosφ = 1)
5 A at 30 VDC with resistive load (cosφ = 1)
Ambient temperature Operating: 10°C to 55°C (with no icing)
Storage: 25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%

Related product manuals