Loading...
Thermocouple Transducer K3FP-TS-UI 17
Thermocouple Transducer
K3FP-TS-UI
6.2-mm Ultra-slim Thermocouple Transducer
Converts measured values for type J and K thermocouple
sensors into analog signals.
Measurement range can be set between 150 and 1,350°C.
Isolates between input, output, and power supply. 1,500 V AC
dielectric strength.
Close mounting.
CE Marking compliant.
UL certified.
Refer to Common Precautions on page 38.
Ordering Information
Thermocouple Transducer
Optional Products
Model Number Structure
1. Model
Type J and K Thermocouples
(Conforms to IEC 60584-1)
2. Output signal
UI: 0 to 20 mA DC, 4 to 20 mA DC,
20 to 0 mA DC, 20 to 4 mA DC,
0 to 5 V DC, 1 to 5 V DC,
0 to 10 V DC, 10 to 0 V DC
(selected by DIP switch setting)
Ratings and Specifications
Ratings and Specifications
Name Model
Thermocouple Transducer K3FP-TS-UI
Name Model
DIN rail bus connector K3FP-1
12
K3FP-TS-UI
Supply voltage 24 V DC
Allowable supply
voltage range
80% to 125% of rated supply voltage
Current consumption 25 mA DC max.
Power consumption 500 mW max.
Error (See note.) Over maximum measurement span:
±0.2%
max.
Over set measurement span: ((150 K/set
measurement span [K])
±0.1)%
Temperature
coefficient
Max. 0.02%/
°C max. (at 23°C)
Cold junction error 3 K (average 2 K)
Response time
(0% to 99%)
30 ms max.
Insulation resistance 10 M
min. between inputs, outputs, and
power supply (at 500 V DC)
Dielectric strength 1,500 V AC, 50 Hz, 1 min (between inputs,
outputs, and power supply)
Noise resistance Conforms to IEC 61000
Ambient operating
temperature
20 to 65°C
Ambient storage
temperature
40 to 85°C
Ambient operating
humidity
95% max. (with no condensation)
Ambient storage
humidity
95% max. (with no condensation)
Connection method Screw connections (M3)
Tightening torque 0.5 N·m

Related product manuals