18 Thermocouple Transducer K3FP-TS-UI
Note: K is the abbreviation for Kelvin, the unit for absolute
temperature.
■ Input Specifications
Note: Set the start and end temperatures using the DIP switch to
50
°C or higher.
■ Output Specifications
Nomenclature
Connecting
cable
Solid
wire
0.14 to 2.5 mm
2
Stranded
wire
0.2 to 2.5 mm
2
AWG 24 to 12
Wire
stripping
length
12 mm
Degree of protection IP20
Housing material PBT
Weight 54 g
Safety standards UL 508
EMC EMI:
Radiated EMI: EN 55011
EMS:
ESD immunity: EN 61000-4-2
Rated electromagnetic field immunity:
EN 61000-4-3
Burst immunity: EN 61000-4-4
Surge immunity: EN 61000-4-5
Conducted disturbance immunity:
EN 61000-4-6
Input signal
Item
Type J and K Thermocouples
(Conforms to IEC 60584-1)
Measurement range J:
−150 to 1,200°C
K:
−150 to 1,350°C
Minimum
measurement span
(See note.)
Min. 50
°C
Max. input signal 30 V
Output signal
Item
0 to 20 mA DC,
4 to 20 mA DC,
20 to 0 mA DC,
20 to 4 mA DC
0 to 5 V DC,
1 to 5 V DC,
0 to 10 V DC,
10 to 0 V DC
Allowable load
impedance
500
Ω max. 10 kΩ min.
Max. output signal 23 mA 12.5 V
Non-load voltage 12.5 V max. ---
Short-circuit current --- 10 mA
Ripple 20 mV pp max.
(500
Ω)
20 mV pp max.
Operation during
sensor faults
0% to 105%
7
8 Supply voltage
5
6 Output signals
Translucent cover
Snap for mounting DIN rail
DIN rail bus connection
Diagnostics indicator (red)
DIP switch S3
DIP switch S2
DIP switch S1
2
3 Inputs: Type J or K thermocouple senso