Thermocouple Transducer K3FP-TS-UI 19
DIP Switch Settings
All DIP switches are turned OFF at shipment.
DIP Switch S1
DIP switch S1 is used to set the thermocouple type, cold junction
compensation enable/disable, output signal range, and the start of
the measurement range.
DIP Switch S3
DIP switch S3 is used to select the current output and voltage output
for output signals.
SWITCH DIP switch S1
ON ●
↑
OFF ❍ ↓
12345678
Thermocouple type
Type J ❍
Type K ●
Cold junction
compensation
enable/disable
Enabled ●
Disabled ❍
Output signal range
0 to 20 mA ❍❍❍
20 to 0 mA ●❍❍
4 to 20 mA ❍● ❍
20 to 4 mA ●●❍
0 to 10 V ❍❍●
10 to 0 V ●❍●
0 to 5 V ❍● ●
1 to 5 V ●●●
Start temperature
[°C] [°F]
032 ❍❍❍
−10 14 ●❍❍
−20 −4 ❍● ❍
−30 −22 ●●❍
−40 −40 ❍❍●
−50 −58 ●❍●
−100 −148 ❍● ●
−150 −238 ●●●
SWITCH DIP switch S3
ON ●
↑
OFF ❍ ↓
12
Output signal
0 to 20 mA
●❍
20 to 0 mA
4 to 20 mA
20 to 4 mA
0 to 10 V
❍●
10 to 0 V
0 to 5 V
1 to 5 V