Thermocouple Transducer K3FP-TS-UI 21
Output Status for Errors
Relationship between Output Signal Range Selection
Output Signal Ranges 0 to 20 mA or 20 to 0 mA
Output Signal Ranges 4 to 20 mA or 20 to 4 mA
Output Signal Ranges 0 to 10 V or 10 to 0 V
Output Signal Range 0 to 5 V
Output Signal Range 1 to 5 V
SWITCH DIP switch S2
ON ●
↑
OFF ❍ ↓
78
Output status
for errors
When disconnected on
thermocouple side
Above measurement range Below measurement range
A ❍❍Held at 5% of maximum rated
output.
Held at 2.5% of maximum rated
output.
Held at minimum rated output.
B ●❍Held at 5% of maximum rated
output.
Held at 2.5% of maximum rated
output.
Held at
−12.5% of minimum rated
output.
C ❍●Held at 5% of maximum rated
output.
Held at maximum rated output. Held at minimum rated output.
D ●●Held at minimum rated output. Held at maximum rated output. Held at minimum rated output.
Output status
for errors
DIP switch S2 When disconnected on
thermocouple side
Above measurement range Below measurement range
7 8
A ❍❍21 mA 20.5 mA 0 mA
B ●❍21 mA 20.5 mA 0 mA
C ❍●21 mA 20 mA 0 mA
D ●●0 mA 20 mA 0 mA
Output status
for errors
DIP switch S2 When disconnected on
thermocouple side
Above measurement range Below measurement range
7 8
A ❍❍21 mA 20.5 mA 4 mA
B ●❍21 mA 20.5 mA 3.5 mA
C ❍●21 mA 20 mA 4 mA
D ●●4 mA 20 mA 4 mA
Output status
for errors
DIP switch S2 When disconnected on
thermocouple side
Above measurement range Below measurement range
7 8
A ❍❍10.5 V 10.25 V 0 V
B ●❍10.5 V 10.25 V 0 V
C ❍●10.5 V 10 V 0 V
D ●●0 V 10 V 0 V
Output status
for errors
DIP switch S2 When disconnected on
thermocouple side
Above measurement range Below measurement range
7 8
A ❍❍5.25 V 5.125 V 0 V
B ●❍5.25 V 5.125 V 0 V
C ❍●5.25 V 5 V 0 V
D ●●0 V5 V0 V
Output status
for errors
DIP switch S2 When disconnected on
thermocouple side
Above measurement range Below measurement range
7 8
A ❍❍5.25 V 5.125 V 1 V
B ●❍5.25 V 5.125 V 0.875 V
C ❍●5.25 V 5 V 1 V
D ●●1 V5 V1 V