EasyManua.ls Logo

Omron K3FP Series - Page 22

Omron K3FP Series
41 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22 Thermocouple Transducer K3FP-TS-UI
Connections
Internal Block Diagram
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Precautions
Refer to pages 38 and 39 for common precautions.
Precautions for Correct Use
Diagnostics Indicator
The diagnostics indicator (LED) inside the translucent cover shows
the error status, as outlined in the following table.
2
3
K3FP-1
TC
CJC
5
6
+
Output signal
7
8
+
Supply voltage
93.1 6.2
102.5
K3FP-TS-UI
Note: 1. Use solid wire with a diameter
of 2.5 mm
2
max. or bar
terminals with insulation
sleeves for terminal
connections.
To preserve dielectric strength
after connection, the length of
the exposed conductive part
inserted into the terminal must
be 12 mm max.
2. Screw Tightening Torque
Recommended torque:
0.5 N·m
12 mm max. 12 mm max.
For 2.5-mm
2
(max.)
solid wire:
For bar terminals with
insulation sleeves:
Indicator
status
Error details
Flashing Measuring range span less than 50 K
The upper limit of the measurement range for a type
J thermocouple is set to 1,200
°C or higher.
Lit Disconnection on the thermocouple side
Short circuit on the thermocouple side
Above measurement range
Below measurement range

Related product manuals