Page #383 background image
A-99
Appendices
NJ-series CPU Unit Hardware User’s Manual (W500)
A-4 Load Short-circuit Protection and Line Disconnection Detection for CJ-series Basic I/O Units
A
A-4-2 Load Short-circuit Protection for CJ1W-OD204/OD212/OD232/MD232
Restrictions
If a short-circuit occurs in an external load, immediately turn OFF the corresponding output and
remove the cause. An alarm output bit that corresponds to the external load output number is turned
ON. There is an alarm output bit for every common.
When an alarm output bit turns ON, use a self-holding bit for the alarm in the user program and turn
OFF the corresponding output.
The Alarm Output Bits are allocated in the Basic I/O Unit Information Area system-defined variable.
Sixteen output bits are assigned for each slot and rack in which a Unit is mounted.
_CJB_IOUnitInfo[rack_number,slot_number,serial_number_in_Unit]
For example, when the CJ1W-OD212 is mounted in slot 0 of rack 0, _CJB_IOUnitInfo[0,0,0]
changes to TRUE if output Ch1Out2 changes to TRUE.
When the CJ1W-OD232 is mounted in slot 1 of rack 2, _CJB_IOUnitInfo[2,1,1] changes to TRUE if
output Ch2Out8 changes to TRUE.

Table of Contents

Questions and Answers:

Omron NJ501-1400 Specifications

General IconGeneral
ModelNJ501-1400
Built-in Ethernet portYes
Built-in USB portYes
Power supply voltage24 VDC
Power consumption30 W
Operating temperature0 to 55 °C
Protection ratingIP20
Cycle Time1 ms
Built-in EtherNet/IP portYes
Built-in EtherCAT portYes
Programming languageIEC 61131-3 (LD, ST, FBD, SFC, IL)
Storage temperature-25 to 70 °C
Operating humidity10 to 90% RH (non-condensing)
Vibration resistance10 to 57 Hz, 0.075 mm amplitude, 57 to 150 Hz, 9.8 m/s² acceleration
Shock resistance150 m/s²