EasyManuals Logo

Omron R88D-KT Series User Manual

Omron R88D-KT Series
634 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #375 background imageLoading...
Page #375 background image
6
6-3
6-1 Damping Control
OMNUC G5-SERIES AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
Applied Functions
Operating Procedure
1. Adjust the position loop gain and speed loop gain.
Adjust Position Loop Gain (Pn100), Speed Loop Gain (Pn101), Speed Loop Integral Time
Constant (Pn102) and Torque Command Filter Time Constant (Pn104).
If no problem occurs in realtime autotuning, you can continue to use the settings.
2. Measure the damping frequency at the tip of the mechanical unit.
Measure the damping frequency by using a measurement device such as a laser displacement
sensor, servo acceleration meter, or acceleration pick-up.
Set the damping frequency in one of Damping Frequency 1 to Damping Frequency 4 (1:
Pn214, 2: Pn216, 3: Pn218, 4: Pn220) according to the operation.
Also set the switching mode using Damping Filter Selection (Pn213).
If the measurement device cannot be used, use CX-Drive tracing function, and read the
residual damping frequency (Hz) from the position error waveform as shown in the following
figure.
If vibration persists after setting the frequency, increase or decrease the damping frequency to
find the frequency at which vibration decreases.
3. Make the damping filter settings.
Make the damping filter settings (1: Pn215, 2: Pn217, 3: Pn219, 4: Pn221).
First, set to 0.
The stabilization time can be reduced by setting a large value; however, torque ripple will
increase at the command change point as shown in the following figure. Set a range that will
not cause torque saturation under actual operation conditions. The effects of vibration
suppression will be lost if torque saturation occurs.
When the Damping Frequency 1 (Pn214) is set, reduce the setting if torque saturation occurs
or increase the setting to increase operation speed. Normally 0 is set.
If the damping filter 1 is enabled, use the following setting range.
Setting range: 100 Pn214 + Pn215 Pn214 × 2 or 2,000
Note: If the damping filter 1 is disabled under Damping Filter Selection (Pn213), this parameter is also
disabled.
The damping frequency in the figure is calculated with
the following formula:
Since the parameter unit is 0.1 Hz:
(Pn214, Pn216, Pn218, Pn220) = 10 × f
Application example
If the damping cycle is 100 ms or 20 ms, set 100 or
500 in the parameter so that the damping frequency
becomes 10 Hz or 50 Hz.
Command
speed
Position error
Calculate the
damping frequency.
Damping cycle T
1
T (s)
f (Hz)
=
Torque command
Torque saturation
Damping filter setting is too large.
Damping filter
setting is appropriate.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron R88D-KT Series and is the answer not in the manual?

Omron R88D-KT Series Specifications

General IconGeneral
BrandOmron
ModelR88D-KT Series
CategoryServo Drives
LanguageEnglish

Related product manuals