Overvoltage Protection ( S82K-24024T Models Only)
The Power Supply is provided with an overvoltage protection function that protects the load and the Power Supply from possible damage by
overvoltage. When the output voltage rises above a set value, the protection function is triggered, shutting off the output voltage. If this occurs,
reset the Power Supply by turning it of f for 1 minute min. and then turning it on again.
Output voltage (V)
Overvoltage
protection
operating
10%
--10%
Rated output
voltage
Variable range
Inrush Current, Start up Time, Hold Time
Input ON
AC input voltage
AC input current
Output voltage
Inrush current on input appli cation
Start up time: 100 to 1000 ms
max. depending on the model.
Hold time
(20 ms min.)
90% 96.5%