EasyManuals Logo

Onan CCKB User Manual

Onan CCKB
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
vibration
isolators
are
for
the
engine
end
only
and
the
other
two
are
for
the
generator
end
only.
Use
them
for
their
respective
positions
or
undesirable
cushioning
will
result.
BATTERY
CONNECTION
VENTILATION
AND
COOLING
Ventilation
and
cooling
for
outdoor
installations
usually
present
no
problems.
Indoor
installations,
however,
require
properly
sized
and
located
vents
for
both
inlet
and
outlet
air.
See
Specifications
section
for
required
airflow.
The
outlet
should
be
slightly
higher
than
the
inlet
for
convection
airflow.
F^ovuie
two
6
volt
batteries
connected
in
series
F
'
1
i
!of
a
12
volt
source.
See
Specifications
tor
n-irarnum
battery
ampere-hour
rating.
Connect
the
battery
positive
(+)
cable
to
the
start
solenoid
(located
in
the
control
box).
Route
the
battery
cable
through
the
rear
of
the
control
box.
Connect
the
battery
negative
(-)
to
a
good
ground
on
the
generator
set
frame.
See
Figures
1
and
3.
Do
not
disconnect
starting
batteries
while
set
is
running.
The
resulting
overvoltage
condi¬
tion
will
damage
electric
choke
and
may
damage
control
com¬
ponents.
Standby
installations:
If
the
installation
is
forstandby
service,
install
a
double-throw
transfer
switch
(either
manual
or
automatic)
to
prevent
feeding
generator
output
into
the
normal
power
source
lines
and
to
also
preventcommercial
powerand
generator
output
from
being
connected
to
the
load
at
the
same
time.
GROUNDING
WARNING
I
prsvent
shock
hazard,
ground
the
set.
Connect
a
#8
or
larger
wire
between:
(1)
a
separate
ground
pipe
or
rod
penetrating
into
moist
earth;
(2)
and
the
solderless
connector
located
on
the
generator
(on
models
not
so
equipped,
to
the
battery
ground
stud
on
the
engine).
See
Figure
3.
The
required
amount
of
air
must
reach
the
unit,
absorb
the
heat
and
be
discharged
away
from
the
installation
area.
When
determining
vent
sizes,
con¬
sider
the
following:
1.
Size
of
enclosure.
2.
Ambient
temperature.
3.
Electrical
load.
4.
Running
time.
5.
Restrictions
screens,
filters,
etc.
6.
Prevailing
wind
direction.
If
the
generating
set
is
enclosed
in
a
small,
poorly
ventilated
enclosure,
auxiliary
fans
can
be
used
to
increase
airflow.
The
air
inlet
to
the
engine
must
not
exceed
120°
F
(49°C)
when
running
atfullload.
If
inlet
air
is
more
than
10°F
(12°C)
above
ambient
air,
there
is
a
good
possibility
that
cooling
air
is
recirculating.
Pressure
Cooling:
These
units
need
an
inlet
vent
with
an
unrestricted
opening
of
2-1/2
square
feet
(2.3
m^).
Install
a
separate
duct
from
the
engine
for
the
discharge
air.
The
discharge
duct
must
be
at
least
as
large
as
the
inlet
vent.
If
a
screen
is
used
in
the
duct,
increase
the
duct
size
proportionately
to
the
screen
restriction.
Use
large
radius
elbows
for
bends
and
increase
the
duct
size
for
runs
overSfeet
(1.5
m).
A
canvas
section
in
the
duct
prevents
transmission
of
vibration.
A
slight
pitch
upward
in
the
duct
lets
heat
escape
when
the
unit
is
stopped
and
minimizes
vapor
lock.
Do
not
use
discharged
air
for
heating
since
it
may
contain
poisonous
gases.
warningI
FIGURE
3.
BATTERY
AND
GROUND
CONNECTIONS
s

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Onan CCKB and is the answer not in the manual?

Onan CCKB Specifications

General IconGeneral
Engine ModelCCKB
Fuel TypeGasoline
Cooling SystemAir-cooled
PhaseSingle-phase
Governor TypeMechanical
Rated RPM1800 RPM
Frequency60 Hz
Ignition SystemBattery Ignition
Starting SystemElectric
Voltage120/240 V
Rated Output4.0 kW (5.0 kVA)
Maximum Output5.5 kW
Oil Capacity2 quarts
Generator TypeRevolving field
Fuel Consumption at Full Load0.75 GPH
Fuel Consumption at Half Load0.4 GPH

Related product manuals