1
1. Running
1.1 Safety Points
• During operation, the unit may have very hot or cold surfaces.
• Thetemperatureprobeisinstalleddirectlyinthesecondaryow.Do
notremovewhenthesystemishot,fullofwaterorunderanypressure.
• Takecarewhenlifting.Onlyusethedesignatedliftingpoint.Useonly
certiedliftingequipmentcapableofliftingtheweight.Residualwater
may also be present and spillage could occur.
• NeverlifttheOrmandyRycroftBreezebyanyassociatedpipeworkor
pipe connections.
• Takecarewhenhandling,assomeedgesmaybesharp.
• Theequipmenthasdangerfromelectricity.Donotremovecoversor
allowanyexposedliveparts.Isolatebeforeworkingontheunit.
• The electrical and mechanical functionality must be considered prior
toconnectinganynonfactoryttedequipment.E.g.pumps,valves,
actuators etc.
• PowersupplyandcontrolsignalcablesMUST be segregated as far as is
reasonably practical.
• Shielded control cables must be used.
• Localauthorityregulationsmustbefollowedatalltimes.
• Ensurealloperationsarecarriedoutbysuitablytrained/qualied
personnel.
Checks
Complete (✓)
Check that electrical installation is complete.
Check that the mechanical installation is complete.
Checkthatthesystemhasbeenushed,butNOT through the plate pack and
that there are no leaks.
Check that any air has been eliminated from the system.
Checkthatvalvesareopenedintherequiredsequence.
1.2 Start Up