OUMAN EH-203OUMAN EH-203OUMAN EH-201/LOUMAN EH-201/L
Ajan asetus
Explanation:
Range:
Factory
Settings
Settings:
Attention!
Additional information about settings
The automatic pre-increase in degrees which
occurs after a reduced operation (nighttime drop)
The pre-increase makes it possible to raise the
room temperature faster to a nominal room
temperature (day temp.) after a reduced
operation (see page 23).
In autumn, the temperature of the supply water is
automatically raised for 20 days through autumn
drying. Autumn drying is activated when the
average temperature in a 24-hour period has
continually been above 7 for a period of at least
20 days and after this drops below 7 . Autumn
drying is activated during the next 20 days
whenever the average temperature in a 24-hour
period is under 7 . The autumn drying setting
indicates how much autumn drying raises the
supply water temperature. The original factory
setting is 2 .
Valve closed during the summer: The outdoor
temp. limit at which the regulator closes the
valve. If the mainten. person has selected "H1
Valve regul" under pump summer stop, the
function is not on in that particular circuit. Select
"H1 Valve close" in pump summer stop for that
function to be on (see p. 26). The factory setting
is hat the alve is closed.
°C
°C
°C
°C
0...25 °C
0...15 °C
5...50 °C
Pre-increase
Autumn dry
Valve close
Pre-increase time
(A mainten. person set)
Nominal
temperature
Reduced temp.
= night drop
Supply water
°C
Room temp.
Spared energy
Average temp.
In a 24-hour
(Outdoor temp.)
A time period
of at least
20 days
7°C7 °C
Autumn drying - function on
123 45 67891011121314151617181920
Time/day
Average 24-hours
temp. curvec
0°C
2°C
19 °C
If pump summer stop
has been selected for
relay 1's control
function, this setting
becomes the pump's
summer stop limit.
ESC - press to return to the previous display
Info button - gives operating instructions
Browse button - moves the cursor up and down
ESC
Group select button - not in use in EH201/L
7
Sun compens.
The room temperature of a house having large
windows with a south exposure rises on a
sunny day even in subzero weather. The
reading indicates the maximum amount that
the sun compensation can drop the supply
water temperature.
A maintenance
person must first set
the length of the
pre-increase time
(see maintenance
mode p 23).
Wind sensor must be
connected (Meas.3 or
net).
Wind compens.
0...7°C
0°C
Wind compensation ratio: A house cools down
in windy weather. In that case the wind
compensation raises the supply water
temperature. The reading indicates the
maximum amount that the wind compensation
can raise the supply water temperature.
0 °C 0...-7 °C
Explanation:
Range:
Factory
Settings
Settings:
Attention!
Sun sensor must be
connected (Meas.3 or
net).
WIND AND SUN COMPENSATION: