3-3. Link Controller Initialization
11/98 3-5 U3-1021
Westinghouse Proprietary Class 2C
7. The LC module will perform a set of self-test diagnostics. Figure 3-1 illustrates
the diagnostic LEDs on the LC Electronics module (refer to
Table 2-9 for LED
descriptions).
8. Observe the following indications:
Each of the set of eight LEDs (1 - 8) will be individually lit and then turned
off in sequence starting with LED 1. When this test is completed, all LEDs
(except P and C) should be off.
The 640 Kbytes of user RAM will be tested. The amount tested will be
displayed on the external personal computer. If the test encounters an error,
LED 1 will be lit and an error message will be written to the external
personal computer.
If the LC boots successfully, the following will occur:
Only LED P (Power OK) will be lit.
The screen on the PC will display the A: \ > prompt.
The internal disk on the LC card is known as Drive A.
The external floppy is known as Drive B.
Figure 3-1. Link Controller Module LED Positions (Top View)
P C E I 1 2 3 4 5 6 7 8
Status LEDs
Electronics Module