3-3. Link Controller Initialization
U3-1021 3-8 11/98
Westinghouse Proprietary Class 2C
5. Copy the following programs and files from Drive C on the PC to the floppy
disk in Drive A.
— FORMAT.COM program (DOS program)
— RLCFLASH.EXE program (on RLC10A disk)
— RLCEXTPC.EXE program (on RLC20A disk)
— Any applicable LC executable programs
— Custom AUTOEXEC.BAT file (required for automatic start-up of the LC
application)
— Any applicable configuration files
6. Install the following jumper in the Base Unit terminal block of the LC module
in order to communicate with the external PC and to boot from the external PC
disk:
• Wire jumper between terminal block positions C7 and C8
7. The baud rate for the Programming Port defaults to 19200 (no jumper installed).
If a baud rate of 9600 is desired, install the following jumper in the Base Unit
terminal block of the LC module:
• Wire jumper between terminal block positions B7 and B8
8. Set the floppy drive as the default disk by typing the following command
(assuming the disk is in Drive A):
C:\>A: