EasyManua.ls Logo

Panasonic Aquarea WH-ADC0309J3E5C - Page 124

Panasonic Aquarea WH-ADC0309J3E5C
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
124 Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Planning
5
Mono-bloc systems
Models Power supply 1 Power supply 2
Phases Max. current
consumption
(A)
Max. power
consumption
(kW)
Min. cable size
(mm²)
Phases Max. current
consumption
(A)
Max. power
consumption
(kW)
Min. cable size
(mm²)
WH-MDC05J3E5 1 12.0 2.59 3 x 1.5 1 13.0 3.0 3 x 1.5
WH-MDC07J3E5 1 17.0 3.71 3 x 2.5 1 13.0 3.0 3 x 1.5
WH-MDC09J3E5 1 17.0 3.83 3 x 2.5 1 13.0 3.0 3 x 1.5
WH-MDC12H6E5 1 24.0 5.30 3 x 4.0 1 26.0 6.0 3 x 4.0
WH-MDC16H6E5 1 26.0 5.74 3 x 4.0 1 26.0 6.0 3 x 4.0
WH-MXC09J3E5 1 29.0 6.27 3 x 4.0 1 13.0 3.0 3 x 4.0
WH-MXC12J6E5 1 29.0 6.27 3 x 4.0 1 26.0 6.0 3 x 4.0
WH-MXC09H3E5 1 29.0 6.27 3 x 4.0 1 13.0 3.0 3 x 4.0
WH-MXC12H6E5 1 29.0 6.27 3 x 4.0 1 26.0 6.0 3 x 4.0
WH-MHF09G3E5 1 28.5 6.09
3 x 4.0 or
3 x 6.0
1 13.0 3.0 3 x 4.0
WH-MHF12G6E5 1 29.0 6.20
3 x 4.0 or
3 x 6.0
1 26.0 6.0 3 x 4.0
RCCB and power supplies
L
1
N
1
L
1
N
L N
L N
1
L
1
N
1
L
1
N
L N
L N
1
L
1
N
1
L
1
N
L N
L N
1
RCCB
Power supplies
Power supply 1 Power supply 2
1
2
Terminals on mono-bloc device
Terminals on disconnector of the power supply
Models Power supply 1 Power supply 2
Phases Max. current
consumption
(A)
Max. power
consumption
(kW)
Min. cable size
(mm²)
Phases Max. current
consumption
(A)
Max. power
consumption
(kW)
Min. cable size
(mm²)
WH-MXC09J3E8 3 14.7 9.99 5 x 1.5 1 13.0 3.0 3 x 1.5
WH-MXC09H3E8 3 14.7 9.96 5 x 1.5 1 13.0 3.0 3 x 2.5
RCCB and power supplies
RCCB
Power supplies
Power supply 1 Power supply 2
1
2
Terminals on mono-bloc unit
Terminals on disconnector of the power supply
L
A1
L
A2
L
A3
L
A1
L
A2
L
A3
N
N
L
L
N
N
L
A1
L
A2
L
A3
L
A1
L
A2
L
A3
N
N
L
L
N
N
L
A1
L
A2
L
A3
L
A1
L
A2
L
A3
N
N
L
L
N
N

Table of Contents