124 Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Planning
5
Mono-bloc systems
Models Power supply 1 Power supply 2
Phases Max. current
consumption
(A)
Max. power
consumption
(kW)
Min. cable size
(mm²)
Phases Max. current
consumption
(A)
Max. power
consumption
(kW)
Min. cable size
(mm²)
WH-MDC05J3E5 1 12.0 2.59 3 x 1.5 1 13.0 3.0 3 x 1.5
WH-MDC07J3E5 1 17.0 3.71 3 x 2.5 1 13.0 3.0 3 x 1.5
WH-MDC09J3E5 1 17.0 3.83 3 x 2.5 1 13.0 3.0 3 x 1.5
WH-MDC12H6E5 1 24.0 5.30 3 x 4.0 1 26.0 6.0 3 x 4.0
WH-MDC16H6E5 1 26.0 5.74 3 x 4.0 1 26.0 6.0 3 x 4.0
WH-MXC09J3E5 1 29.0 6.27 3 x 4.0 1 13.0 3.0 3 x 4.0
WH-MXC12J6E5 1 29.0 6.27 3 x 4.0 1 26.0 6.0 3 x 4.0
WH-MXC09H3E5 1 29.0 6.27 3 x 4.0 1 13.0 3.0 3 x 4.0
WH-MXC12H6E5 1 29.0 6.27 3 x 4.0 1 26.0 6.0 3 x 4.0
WH-MHF09G3E5 1 28.5 6.09
3 x 4.0 or
3 x 6.0
1 13.0 3.0 3 x 4.0
WH-MHF12G6E5 1 29.0 6.20
3 x 4.0 or
3 x 6.0
1 26.0 6.0 3 x 4.0
RCCB and power supplies
L
1
N
1
L
1
N
L N
L N
1
RCCB
Power supplies
Power supply 1 Power supply 2
1
2
Terminals on mono-bloc device
Terminals on disconnector of the power supply
Models Power supply 1 Power supply 2
Phases Max. current
consumption
(A)
Max. power
consumption
(kW)
Min. cable size
(mm²)
Phases Max. current
consumption
(A)
Max. power
consumption
(kW)
Min. cable size
(mm²)
WH-MXC09J3E8 3 14.7 9.99 5 x 1.5 1 13.0 3.0 3 x 1.5
WH-MXC09H3E8 3 14.7 9.96 5 x 1.5 1 13.0 3.0 3 x 2.5
RCCB and power supplies
RCCB
Power supplies
Power supply 1 Power supply 2
1
2
Terminals on mono-bloc unit
Terminals on disconnector of the power supply
L
A1
L
A2
L
A3
L
A1
L
A2
L
A3
N
N
L
L
N
N