125
Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Planning
5
Models Power supply 1 Power supply 2
Phases Max. current
consumption
(A)
Max. power
consumption
(kW)
Min. cable size
(mm²)
Phases Max. current
consumption
(A)
Max. power
consumption
(kW)
Min. cable size
(mm²)
WH-MXC12J9E8 3 11.8 7.93 5 x 1.5 3 13.0 9.0 5 x 1.5
WH-MXC16J9E8 3 5 x 2.5 3 5 x 1.5
WH-MXC12H9E8 3 11.9 7.96 5 x 1.5 3 13.0 9.0 5 x 1.5
WH-MXC16H9E8 3 15.5 10.48 5 x 1.5 3 13.0 9.0 5 x 1.5
RCCB and power supply
A1
L
A2
L
A3
N
L
L
A1
L
A2
L
A3
N
L
C1
L
C2
L
C3
N
L
C1
L
C2
L
C3
N
A1
L
A2
L
A3
N
L
L
A1
L
A2
L
A3
N
L
C1
L
C2
L
C3
N
L
C1
L
C2
L
C3
N
RCCB
Power supplies
Power supply 1 Power supply 2
1
2
Terminals on mono-bloc unit
Terminals on disconnector of the power supply
Connection conditions
For mono-bloc units of the J and H generation
For the connection to the power supply, an approved polychloroprene-sheathed
power cord, type designation 60245 IEC 57 or heavier cord, is to be used for mains
connection 1 and mains connection 2.
For mono-bloc unit WH-MDC05J3E5:
The equipment’s power supply 1 complies with IEC/EN 61000-3-2.
The equipment’s power supply 1 complies with IEC/EN 61000-3-3 and can be
connected to current supply network.
The equipment’s power supply 2 complies with IEC/EN 61000-3-2.
The equipment’s power supply 2 complies with IEC/EN 61000-3-11 and shall be
connected to suitable supply network, with the following maximum permissible system
impedance Z
max
= 0.450 Ω at the interface. Please liaise with supply authority to
ensure that the power supply 2 is connected only to a supply of that impedance or
less.
For mono-bloc unit WH-MDC07J3E5 or WH-MDC09J3E5:
This equipment’s power supply 1 complies with IEC/EN 61000-3-12.
The equipment’s power supply 1 complies with IEC/EN 61000-3-11 and shall be
connected to a suitable supply network, having services current capacity ≥ 100 A
per phase. Please liaise with supply authority that the service current capacity at the
interface point is su󰀩cient for the installation of the equipment.
The equipment’s power supply 2 complies with IEC/EN 61000-3-2.
The equipment’s power supply 2 complies with IEC/EN 61000-3-11 and shall be
connected to suitable supply network, with the following maximum permissible system
impedance Z
max
= 0.450 Ω at the interface. Please liaise with supply authority to
ensure that the power supply 2 is connected only to a supply of that impedance or
less.