210 Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Appendix
8
27
EN
Menus
Menu Default Setting Setting Options / Display
0:30
Delay timer to stop
the bivalent heat
source
(in hour and minutes)�
Control pattern Advanced parallel DHW Yes
•DHW Tank is activated only after selecting
“Yes”�
0:30
Delay timer to start
the bivalent heat
source
(in hour and minutes)�
SG ready input control for
bivalent system follow below
input condition�
Yes SG ready
OFF
Option to set external
pump either ON or
OFF during bivalent
operation� Set to ON
if system is simple
bivalent connection�
SG signal Operation pattern
Vcc-bit1 Vcc-bit2
Open Open
Heat Pump OFF,
Boiler OFF
Short Open
Heat Pump ON,
Boiler OFF
Open Short
Heat Pump OFF,
Boiler ON
Short Short
Heat Pump ON,
Boiler ON
5.10
External SW
No
5.11
Solar connection
•The optional PCB connectivity
must be selected YES to
enable the function�
•If the optional PCB
connectivity is not selected,
the function will not appear on
the display
•DHW is not applicable for
WH-ADC *models�
No
Yes
Buffer tank Selection of the tank
Yes After selecting the tank
10 °C
Set
T ON
temperature