46 Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Product Description
4
All in One Compact systems | T-CAP | H Generation | Single Phase | Heating and Cooling | R410A
Single phase (Power to indoor)
Kit KIT‑AXC09HE5C KIT‑AXC12HE5C
Heating capacity / COP (A +7 °C, W 35 °C) kW / – 9.00 / 4.84 12.00 / 4.74
Heating capacity / COP (A +7 °C, W 55 °C) kW / – — / — — / —
Heating capacity / COP (A +2 °C, W 35 °C) kW / – 9.00 / 3.59 12.00 / 3.44
Heating capacity / COP (A +2 °C, W 55 °C) kW / – — / — — / —
Heating capacity / COP (A -7 °C, W 35 °C) kW / – — / — — / —
Heating capacity / COP (A -7 °C, W 55 °C) kW / – — / — — / —
Cooling capacity / EER (A 35 °C, W 7 °C) kW / – 7.00 / 3.17 10.00 / 2.81
Cooling capacity / EER (A 35 °C, W 18 °C) kW / – — / — — / —
ErP data for Space Heating
Average climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 181 / 130 170 / 130
SCOP W35 / W55 4.59 / 3.32 4.32 / 3.32
Energy class
1
W35 / W55 A+++ / A++ A++ / A++
Warm climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 235 / 158 231 / 158
SCOP W35 / W55 5.95 / 4.02 5.86 / 4.02
Energy class
1
W35 / W55 A+++ / A+++ A+++ / A+++
Cold climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 160 / 125 160 / 125
SCOP W35 / W55 4.08 / 3.20 4.08 / 3.20
Energy class
1
W35 / W55 A++ / A++ A++ / A++
Indoor unit WH‑ADC1216H6E5C WH‑ADC1216H6E5C
Sound pressure Heat / Cool dB(A) 33 / 33 33 / 33
Dimension H x W x D mm 1,640 x 598 x 600 1,640 x 598 x 600
Net weight kg 101 101
Water pipe connector Inch R 1¼ R 1¼
A class pump
Number of speeds Variable Speed Variable Speed
Input power (Min / Max) W — / — — / —
Heatingwaterow(∆T=5K.35°C) l/min 25.80 34.40
Capacity of integrated electric heater kW 6.00 6.00
Recommended fuse A — / — — / —
Recommended cable size, supply 1 / 2 mm² — / — — / —
Water volume l 185 185
Maximum water temperature °C 60 60
Material inside tank Stainless steel Stainless steel
TappingproleaccordingEN16147 — —
ErP data for Water Heating
Average climate
Seasonalenergyefciency(ηw,h) % 92 92
SCOP 2.30 2.30
Energy class
2
— —
Warm climate
Seasonalenergyefciency(ηw,h) % 107 107
SCOP 2.67 2.67
Energy class
2
— —
Cold climate
Seasonalenergyefciency(ηw,h) % 72 72
SCOP 1.81 1.81
Energy class
2
— —
Outdoor unit WH‑UX09HE5 WH‑UX12HE5
Sound power
3
Heat dB(A) 66 66
Dimension / Net weight H x W x D mm / kg 1,340 x 900 x 320 / 101 1,340 x 900 x 320 / 101
Refrigerant (R410A) / CO
2
Eq. kg / t 2.85 / 5.951 2.85 / 5.951
Pipe diameter Liquid / Gas Inch (mm) 3/8 (9.52) / 5/8 (15.88) 3/8 (9.52) / 5/8 (15.88)
Pipe length range / Elevation difference (in/out) m / m 3 ~ 30 / 20 3 ~ 30 / 20
Pipe length for additional gas / Additional gas amount m / g/m 10 / 50 10 / 50
Operation range
Outdoor ambient
Heat °C -28 ~ +35 -28 ~ +35
Cool °C +16 ~ +43 +16 ~ +43
Water outlet
Heat °C 20 ~ 60 20 ~ 60
Cool °C 5 ~ 20 5 ~ 20
1 Scale from A+++ to D.
2 Scale from A+ to F.
3 Sound power in accordance to 811/2013, 813/2013 and EN12102-1:2017 at +7 °C.
Notes:
EER and COP calculation is based in accordance to EN14511.
This product is designed to comply with the European Water Quality Directive 98/83/EC amended by 2015/1787/EU. The lifespan of the product is not guaranteed in the case of the use of
groundwater, such as spring water or well water, the use of tap water when salt or other impurities are contained, nor in areas of acidic water quality. Maintenance and warranty costs related to
these cases are the customer’s responsibility.