48 Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Product Description
4
Bi-bloc systems | Aquarea High Performance | H Generation | Single Phase / Three Phase | Heating and
Cooling | R410A
Single phase Three phase (Power to indoor)
Kit KIT‑WC12H6E5 KIT‑WC16H6E5 KIT‑WC09H3E8 KIT‑WC12H9E8 KIT‑WC16H9E8
Heating capacity / COP (A +7 °C, W 35 °C) kW / – 12.00 / 4.74 16.00 / 4.28 9.00 / 4.84 12.00 / 4.74 16.00 / 4.28
Heating capacity / COP (A +7 °C, W 55 °C) kW / – 12.00 / 2.93 14.50 / 2.72 9.00 / 2.94 12.00 / 2.93 14.50 / 2.72
Heating capacity / COP (A +2 °C, W 35 °C) kW / – 11.40 / 3.44 13.00 / 3.28 9.00 / 3.59 11.40 / 3.44 13.00 / 3.28
Heating capacity / COP (A +2 °C, W 55 °C) kW / – 9.10 / 2.23 9.80 / 2.21 8.80 / 2.23 9.10 / 2.23 9.80 / 2.21
Heating capacity / COP (A -7 °C, W 35 °C) kW / – 10.00 / 2.73 11.40 / 2.57 9.00 / 2.85 10.00 / 2.73 11.40 / 2.57
Heating capacity / COP (A -7 °C, W 55 °C) kW / – 8.20 / 1.95 9.00 / 1.85 7.90 / 2.05 8.20 / 1.95 9.00 / 1.85
Cooling capacity / EER (A 35 °C, W 7 °C) kW / – 10.00 / 2.81 12.20 / 2.56 7.00 / 3.17 10.00 / 2.85 12.20 / 2.56
Cooling capacity / EER (A 35 °C, W 18 °C) kW / – 10.00 / 4.17 12.20 / 4.12 7.00 / 4.67 10.00 / 4.26 12.20 / 4.12
ErP data for Space Heating
Average climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 190 / 134 190 / 130 190 / 133 190 / 134 190 / 130
SCOP W35 / W55 4.82 / 3.42 4.82 / 3.33 4.81 / 3.41 4.82 / 3.42 4.82 / 3.33
Energy class
1
W35 / W55 A+++ / A++ A+++ / A++ A+++ / A++ A+++ / A++ A+++ / A++
Warm climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 245 / 159 245 / 169 245 / 159 245 / 159 245 / 169
SCOP W35 / W55 6.21 / 4.05 6.21 / 4.30 6.21 / 4.05 6.21 / 4.05 6.20 / 4.30
Energy class
1
W35 / W55 A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++
Cold climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 168 / 121 168 / 121 168 / 121 168 / 121 168 / 121
SCOP W35 / W55 4.29 / 3.10 4.28 / 3.10 4.28 / 3.10 4.29 / 3.10 4.28 / 3.10
Energy class
1
W35 / W55 A++ / A+ A++ / A+ A++ / A+ A++ / A+ A++ / A+
Indoor unit WH‑SDC12H6E5 WH‑SDC16H6E5 WH‑SDC09H3E8 WH‑SDC12H9E8 WH‑SDC16H9E8
Sound pressure Heat / Cool dB(A) 33 / 33 33 / 33 33 / 33 33 / 33 33 / 33
Dimension H x W x D mm 892 x 500 x 340 892 x 500 x 340 892 x 500 x 340 892 x 500 x 340 892 x 500 x 340
Net weight kg 43 44 43 44 45
Water pipe connector Inch R 1¼ R 1¼ R 1¼ R 1¼ R 1¼
A class pump
Number of speeds Variable Speed Variable Speed Variable Speed Variable Speed Variable Speed
Input power (Min / Max) W 34 / 110 30 / 105 32 / 102 34 / 110 30 / 105
Heatingwaterow(∆T=5K.35°C) l/min 34.4 45.9 25.8 34.4 45.9
Capacity of integrated electric heater kW 6 6 3 9 9
Recommended fuse A 30 / 30 30 / 30 15 / 30 15 / 30 15 / 30
Recommended cable size, supply 1 / 2 mm² 3 x 4.0 or 6.0 / 3 x 4.0 3 x 4.0 or 6.0 / 3 x 4.0 5 x 1.5 / 5 x 1.5 5 x 1.5 / 5 x 1.5 5 x 1.5 / 5 x 1.5
Outdoor unit WH‑UD12HE5 WH‑UD16HE5 WH‑UD09HE8 WH‑UD12HE8 WH‑UD16HE8
Sound power
2
Heat dB(A) 65 65 65 65 65
Dimension H x W x D mm 1,340 x 900 x 320 1,340 x 900 x 320 1,340 x 900 x 320 1,340 x 900 x 320 1,340 x 900 x 320
Net weight kg 101 101 107 107 107
Refrigerant (R410A) / CO
2
Eq. kg / t 2.55 / 5.324 2.55 / 5.324 2.55 / 5.324 2.55 / 5.324 2.55 / 5.324
Pipe diameter Liquid / Gas Inch (mm) 3/8 (9.52) / 5/8 (15.88) 3/8 (9.52) / 5/8 (15.88) 3/8 (9.52) / 5/8 (15.88) 3/8 (9.52) / 5/8 (15.88) 3/8 (9.52) / 5/8 (15.88)
Pipe length range m 3 ~ 50 3 ~ 50 3 ~ 30 3 ~ 30 3 ~ 30
Elevation difference (in/out) m 30 30 20 20 20
Pipe length for additional gas m 10 10 10 10 10
Additional gas amount g/m 50 50 50 50 50
Operation range
Outdoor ambient
Heat °C -20 ~ +35 -20 ~ +35 -20 ~ +35 -20 ~ +35 -20 ~ +35
Cool °C +16 ~ +43 +16 ~ +43 +16 ~ +43 +16 ~ +43 +16 ~ +43
Water outlet
Heat °C 20 ~ 55 20 ~ 55 20 ~ 55 20 ~ 55 20 ~ 55
Cool °C 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20
1 Scale from A+++ to D.
2 Sound power in accordance to 811/2013, 813/2013 and EN12102-1:2017 at +7 °C.
Note: