Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Product Description
4
Mono-bloc systems | Aquarea T-CAP | J Generation | Single Phase / Three Phase | Heating and
Cooling | R32
Single phase Three phase
Outdoor unit WH‑MXC09J3E5 WH‑MXC12J6E5 WH‑MXC09J3E8
5
WH‑MXC12J9E8
5
WH‑MXC16J9E8
5
Heating capacity / COP (A +7 °C, W 35 °C) kW / – 9.00 / 5.08 12.00 / 4.80 9.00 / — 12.00 / — 16.00 / —
Heating capacity / COP (A +7 °C, W 55 °C) kW / – 9.00 / 3.08 12.00 / 3.05
Heating capacity / COP (A +2 °C, W 35 °C) kW / – 9.00 / 3.81 12.00 / 3.53 9.00 / — 12.00 / — 16.00 / —
Heating capacity / COP (A +2 °C, W 55 °C) kW / – 9.00 / 2.54 12.00 / 2.42
Heating capacity / COP (A -7 °C, W 35 °C) kW / – 9.00 / 3.08 12.00 / 2.82
Heating capacity / COP (A -7 °C, W 55 °C) kW / – 9.00 / 2.12 12.00 / 2.00
Cooling capacity / EER (A 35 °C, W 7 °C) kW / – 9.00 / 3.18 12.00 / 2.90 9.00 / — 12.00 / — 14.50 / —
Cooling capacity / EER (A 35 °C, W 18 °C) kW / – 9.00 / 4.62 12.00 / 3.95
ErP data for Space Heating
Average climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 195 / 140 195 / 140
SCOP W35 / W55 4.96 / 3.57 4.96 / 3.57
Energy class
1
W35 / W55 A+++ / A++ A+++ / A++ A+++ / A++ A+++ / A++ A++ / A++
Warm climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 256 / 171 256 / 171
SCOP W35 / W55 6.47 / 4.34 6.47 / 4.34
Energy class
1
W35 / W55 A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++
Cold climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 169 / 127 169 / 127
SCOP W35 / W55 4.31/ 3.26 4.31 / 3.26
Energy class
1
W35 / W55 A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++
Sound power
2
Heat dB(A) 65 65 65 65 66
Dimension H x W x D mm 1,410 x 1,283 x 320 1,410 x 1,283 x 320 1,410 x 1,283 x 320 1,410 x 1,283 x 320 1,410 x 1,283 x 320
Net weight kg 140 140 151 151 164
Refrigerant (R32) / CO
2
Eq.
3
kg / t 1.60 / 1.080 1.60 / 1.080 1.60 / 1.080 1.60 / 1.080 1.80 / 1.215
Water pipe connector Inch R 1¼ R 1¼ R 1¼ R 1¼ R 1¼
Pump
Number of speeds Variable Speed Variable Speed Variable Speed Variable Speed Variable Speed
Input power (Min / Max) W 32 / 102 34 / 110 32 / 102 34 / 110 38 / 120
Heatingwaterow(∆T=5K.35°C) l/min 25.8 34.4 25.8 34.4 45.9
Capacity of integrated electric heater kW 3 6 3 9 9
Input power
Heat kW 1.77 2.50 1.77 2.50
Cool kW 2.83 4.14 2.83 4.14
Running and starting
current
Heat A 8.3 11.6
Cool A 13.1 19.1
Current 1 A 29.0 29.0 14.7 11.9 15.5
Current 2 A 13.0 26.0 13.0 13.0 13.0
Recommended fuse, supply 1 / 2 A 30 / 30 30 / 30 20 / 16 20 / 20 20 / 20
Recommended cable size, supply 1 / 2 mm² 3 x 4.0 or 6.0 / 3 x 4.0 3 x 4.0 or 6.0 / 3 x 4.0 5 x 1.5 / 3 x 1.5 5 x 1.5 / 5 x 1.5 5 x 2.5 / 5 x 1.5
Operation range
Outdoor ambient
Heat °C -20 ~ +35 -20 ~ +35 -20 ~ +35 -20 ~ +35 -20 ~ +35
Cool °C 10 ~ +43 10 ~ +43 10 ~ +43 10 ~ +43 10 ~ +43
Water outlet
4
Heat °C 20 ~ 65 20 ~ 65 20 ~ 65 20 ~ 65 20 ~ 65
Cool °C 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20
1 Scale from A+++ to D.
2 Sound power in accordance to 811/2013, 813/2013 and EN12102-1:2017 at +7 °C.
3 WH-MXC models are hermetically sealed.
4 A water outlet temperature of 65 °C is only possible if ΔT is manually set to 15 °C on the remote controller and ambient temperatures are between 5 and 20 °C. Otherwise max. water outlet
temperature is 60 °C.
5 All data is tentative.
Note:
EER and COP calculation is based in accordance to EN14511.