Loading...
58 Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Product Description
4
Mono-bloc systems | Aquarea T-CAP | H Generation | Single Phase / Three Phase | Heating and
Cooling | R410A
Single phase Three phase
Outdoor unit WH‑MXC09H3E5 WH‑MXC12H6E5 WH‑MXC09H3E8 WH‑MXC12H9E8 WH‑MXC16H9E8
Heating capacity / COP (A +7 °C, W 35 °C) kW / – 9.00 / 4.84 12.00 / 4.74 9.00 / 4.84 12.00 / 4.74 16.00 / 4.28
Heating capacity / COP (A +7 °C, W 55 °C) kW / – 9.00 / 2.94 12.00 / 2.88 9.00 / 2.94 12.00 / 2.88 16.00 / 2.71
Heating capacity / COP (A +2 °C, W 35 °C) kW / – 9.00 / 3.59 12.00 / 3.44 9.00 / 3.59 12.00 / 3.44 16.00 / 3.10
Heating capacity / COP (A +2 °C, W 55 °C) kW / – 9.00 / 2.21 12.00 / 2.19 9.00 / 2.21 12.00 / 2.19 16.00 / 2.13
Heating capacity / COP (A -7 °C, W 35 °C) kW / – 9.00 / 2.85 12.00 / 2.72 9.00 / 2.85 12.00 / 2.72 16.00 / 2.49
Heating capacity / COP (A -7 °C, W 55 °C) kW / – 9.00 / 2.02 12.00 / 1.92 9.00 / 2.02 12.00 / 1.92 16.00 / 1.86
Cooling capacity / EER (A 35 °C, W 7 °C) kW / – 7.00 / 3.17 10.00 / 2.81 7.00 / 3.17 10.00 / 2.81 12.20 / 2.56
Cooling capacity / EER (A 35 °C, W 18 °C) kW / – 7.00 / 5.19 10.00 / 5.13 7.00 / 5.19 10.00 / 5.13 12.20 / 3.49
ErP data for Space Heating
Average climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 181 / 130 170 / 130 181 / 130 170 / 130 160 / 125
SCOP W35 / W55 4.59 / 3.32 4.32 / 3.32 4.59 / 3.32 4.32 / 3.32 4.08 / 3.20
Energy class
1
W35 / W55 A+++ / A++ A++ / A++ A+++ / A++ A++ / A++ A++ / A++
Warm climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 235 / 158 231 / 158 235 / 158 231 / 158 231 / 159
SCOP W35 / W55 5.95 / 4.03 5.86 / 4.02 5.95 / 4.02 5.86 / 4.02 5.86 / 4.05
Energy class
1
W35 / W55 A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++
Cold climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 160 / 125 160 / 125 160 / 125 160 / 125 150 / 125
SCOP W35 / W55 4.08 / 3.20 4.08 / 3.20 4.08 / 3.20 4.08 / 3.20 3.83 / 3.20
Energy class
1
W35 / W55 A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++
Sound power
2
Heat dB(A) 65 65 65 65 66
Dimension H x W x D mm 1,410 x 1,283 x 320 1,410 x 1,283 x 320 1,410 x 1,283 x 320 1,410 x 1,283 x 320 1,410 x 1,283 x 320
Net weight kg 142 142 151 151 164
Refrigerant (R410A) / CO
2
Eq.
3
kg / t 2.30 / 4.802 2.30 / 4.802 2.30 / 4.802 2.30 / 4.802 2.35 / 4.907
Water pipe connector Inch R 1¼ R 1¼ R 1¼ R 1¼ R 1¼
Pump
Number of speeds Variable Speed Variable Speed Variable Speed Variable Speed Variable Speed
Input power (Min / Max) W 32 / 102 34 / 110 32 / 102 34 / 110 38 / 120
Heatingwaterow(∆T=5K.35°C) l/min 25.8 34.4 25.8 34.4 45.9
Capacity of integrated electric heater kW 3 6 3 9 9
Input power
Heat kW 1.86 2.53 1.86 2.53 3.74
Cool kW 2.21 3.56 2.21 3.56 4.76
Running and starting
current
Heat A 8.8 11.7 3.0 4.0 5.7
Cool A 10.4 16.5 3.5 5.3 7.1
Current 1 A 29.0 29.0 14.7 11.9 15.5
Current 2 A 13.0 26.0 13.0 13.0 13.0
Recommended fuse A 30 / 30 30 / 30 16 / 16 16 / 16 16 / 16
Recommended cable size, supply 1 / 2 mm² 3 x 4.0 or 6.0 / 3 x 4.0 3 x 4.0 or 6.0 / 3 x 4.0 5 x 1.5 / 3 x 1.5 5 x 1.5 / 5 x 1.5 5 x 1.5 / 5 x 1.5
Operation range
Outdoor ambient
Heat °C -20 ~ +35 -20 ~ +35 -20 ~ +35 -20 ~ +35 -20 ~ +35
Cool °C +16 ~ +43 +16 ~ +43 +16 ~ +43 +16 ~ +43 +16 ~ +43
Water outlet
Heat °C 20 ~ 60 20 ~ 60 20 ~ 60 20 ~ 60 20 ~ 60
Cool °C 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20
1 Scale from A+++ to D.
2 Sound power in accordance to 811/2013, 813/2013 and EN12102-1:2017 at +7 °C.
3 WH-MXC models are hermetically sealed.
Note:
EER and COP calculation is based in accordance to EN14511.