EasyManua.ls Logo

Panasonic Aquarea WH-SDC09H3E5-1 - Page 25

Panasonic Aquarea WH-SDC09H3E5-1
117 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
44 Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Product Description
45
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Product Description
Split systems with hydro-module / T-CAP model series / H Generation / SQ version
T-CAP model series Three-phase (400 V / 50 Hz), heating and cooling, noise-proofed version
Hydro-module WH-SQC09H3E8 WH-SQC12H9E8 WH-SQC16H9E8
Outdoor unit WH-UQ09HE8 WH-UQ12HE8 WH-UQ16HE8
Set (hydro-module + outdoor unit) KIT-WQC09H3E8 KIT-WQC12H9E8 KIT-WQC16H9E8
Model B7 B7 B7
Heatingcapacityat+7°C(A7/W35) kW 9.00 12.00 16.00
COPat+7°C(A7/W35) 4.84 4.14 4.28
Heatingcapacityat+2°C(A2/W35) kW 9.00 11.40 13.00
COPat+2°C(A2/W35) 3.59 3.44 3.28
Heating capacity at -7 °C (A–7/W35) kW 9.00 10.00 11.40
COP at -7 °C (A–7/W35) 2.85 2.73 2.68
Cooling capacity at 35 °C (A35/W7) kW 7.00 10.00 12.20
EER(energyefciencyratio)at35°C(A35/W7) 3.17 2.81 2.56
Energyefciencyclass
1
at 35 / 55 °C
i / i i / i i / i
Hydro-module
Sound pressure level Heating / Cooling dB(A) 33 / 33 33 / 33 33 / 33
Dimensions HxLxW mm 892 x 500 x 340 892 x 500 x 340 892 x 500 x 340
Weight kg 43 44 45
Water-side connection mm 28 28 28
Highefciencypump
Rotation speed stages Variable Variable Variable
Powerconsumption(min./max.)
W 32 / 102 34 / 110 30 / 105
Waterowrate(A7/W35) l/min 25.8 34.4 45,9
Power of E-heating element kW 3 9 9
Power consumption Heating / Cooling kW 1.86/2.21 2.53/3.56 3.74/4.76
Operating and start up current Heating / Cooling A 2.8/3.4 3.9/5.4 5.7/7.2
Max.powerconsumptiononnetworkconnection1/2 A 14.7/13.0 11.9/13.0 15.5/13.0
Recommended fuse for network connection 1 / 2 A 16 / 16 16 / 16 16 / 16
Recommended cable cross section for network connection 1 / 2
mm² 5x1.5/3x1.5 5x1.5/5x1.5 5x1.5/5x1.5
Outdoor unit
Sound pressure level Heating / Cooling dB(A) 47 / 48 48 / 49 51 / 53
Dimensions HxLxW mm 1,410 x 1,283 x 320 1,410 x 1,283 x 320 1,410 x 1,283 x 320
Weight kg 151 151 161
Linediameter Fluid line mm (inches) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Gasline mm (inches) 15.88(5/8) 15.88(5/8) 15.88(5/8)
Pre-lledrefrigerant(R410A)/CO
2
-equivalent kg / t CO
2
-Equ. 2.85/5.951 2.85/5.951 2.99/6.243
Connection distance m 3 – 30 3 – 30 3 – 30
Nominal connection distance m 5 5 5
Pre-lledconnectiondistance m 10 10 10
Additionalcoolantll-upquantity(R410A) g/m 50 50 50
Max.heightdifferenceIU/OU m 20 20 20
Operating range Outside temperature (H / K) °C -20 to 35 / 16 to 43 -20 to 35 / 16 to 43 -20 to 35 / 16 to 43
Water outlet temperature (H / K)
°C 20 to 60 / 5 to 20 25 to 60 / 5 to 20 25 to 60 / 5 to 20
The COP details relate to 230 V in conformance with the EC Directives 2003/32/EC. Power details in conformance with EN 14511.
The information about the energy efciency classes is based on the ofcial ErP specications (EU Ordinance No. 811/2013, EN 14511 and EN 14825) for heat pumps, which have been in
force since 26. September 2015. Other ErP relevant information is included in the respective product data sheets.
Authorised Service Partners or installation companies can activate the cooling function via a special setting.
1 Energy efciency class scale from A++ to G.
Split systems with hydro-module / T-CAP model series / H Generation / Standard
T-CAP model series Single-phase (230 V / 50 Hz), Heating and Cooling Three-phase (400 V / 50 Hz), heating and cooling
Hydro-module WH-SXC09H3E5 WH-SXC12H6E5 WH-SXC09H3E8 WH-SXC12H9E8 WH-SXC16H9E8
Outdoor unit WH-UX09HE5 WH-UX12HE5 WH-UX09HE8 WH-UX12HE8 WH-UX16HE8
Set (hydro-module + outdoor unit) KIT-WXC09H3E5 KIT-WXC12H6E5 KIT-WXC09H3E8 KIT-WXC12H9E8 KIT-WXC16H9E8
Model B6 B6 B6 B6 B6
Heatingcapacityat+7°C(A7/W35) kW 9.00 12.00 9.00 12.00 16.00
COPat+7°C(A7/W35) 4.84 4.74 4.84 4.74 4.28
Heatingcapacityat+2°C(A2/W35) kW 9.00 12.00 9.00 12.00 16.00
COPat+2°C(A2/W35) 3.59 3.44 3.59 3.44 3.10
Heating capacity at -7 °C (A–7/W35) kW 9.00 12.00 9.00 12.00 16.00
COP at -7 °C (A–7/W35) 2.85 2.72 2.85 2.72 2.49
Cooling capacity at 35 °C (A35/W7) kW 7.00 10.00 7.00 10.00 12.20
EER(energyefciencyratio)at35°C(A35/W7) 3.17 2.81 3.17 2.81 2.57
Energyefciencyclass
1
at 35 / 55 °C
i / i i / i i / i i / i i / i
Hydro-module
Dimensions HxLxW mm 892 x 502 x 353 892 x 502 x 353 892 x 502 x 353 892 x 502 x 353 892 x 502 x 353
Weight kg 44 45 45 46 52
Water-side connection mm 28 28 28 28 28
Highefciencypump
Rotation speed stages Variable Variable Variable Variable Variable
Powerconsumption(min./max.)
W 32 / 102 34 / 110 32 / 102 34 / 110 30 / 105
Waterowrate(A7/W35) l/min 25.8 34.4 25.8 34.4 45,9
Power of E-heating element kW 3 6 3 9 9
Power consumption Heating / Cooling kW 1.86/2.21 2.53/3.56 1.86/2.21 2.53/3.56 3.74/4.76
Operating and start up current Heating / Cooling A 8.6/10.2 11.7/16.5 2.8/3.4 3.9/5.4 5.7/7.2
Max.powerconsumptiononnetworkconnection1/2 A 25.0/13.0 29.0/26.0 14.7/13.0 11.9/13.0 15.5/13.0
Recommended fuse for network connection 1 / 2 A 30 / 30 30 / 30 16 / 16 16 / 16 16 / 16
Recommended cable cross section for network connection 1 / 2
mm² 3x4.0or6.0/3x4.0 3x4.0or6.0/3x4.0 5x1.5/3x1.5 5x1.5/5x1.5 5x1.5/5x1.5
Outdoor unit
Sound pressure level Heating / Cooling dB(A) 51 / 49 52 / 50 51 / 49 52 / 50 55 / 54
Dimensions HxLxW mm 1,340 x 900 x 320 1,340 x 900 x 320 1,340 x 900 x 320 1,340 x 900 x 320 1,340 x 900 x 320
Weight kg 101 101 109 109 119
Linediameter Fluid line mm (inches) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Gasline mm (inches) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8)
Pre-lledrefrigerant(R410A)/CO
2
-equivalent kg / t CO
2
-Equ. 2.85/5.951 2.85/5.951 2.85/5.951 2.85/5.951 2.90/6.243
Connection distance m 3 – 30 3 – 30 3 – 30 3 – 30 3 – 30
Nominal connection distance m 7 7 7 7 7
Pre-lledconnectiondistance m 10 10 10 10 10
Additionalcoolantll-upquantity(R410A) g/m 50 50 50 50 50
Max.heightdifferenceIU/OU m 20 20 20 20 20
Operating range Outside temperature (H / K) °C -20 to 35 / 16 to 43 -20 to 35 / 16 to 43 -20 to 35 / 16 to 43 -20 to 35 / 16 to 43 -20 to 35
Water outlet temperature (H / K)
°C 25 to 55 / 5 to 20 25 to 55 / 5 to 20 25 to 60 / 5 to 20 25 to 60 / 5 to 20 25 to 60 / 5 to 20
The COP details relate to 230 V in conformance with the EC Directives 2003/32/EC. Power details in conformance with EN 14511.
The information about the energy efciency classes is based on the ofcial ErP specications (EU Ordinance No. 811/2013, EN 14511 and EN 14825) for heat pumps, which have been
in force since 26. September 2015. The efciency classes marked with an asterisk (*) correspond to the new A+++ class to be introduced starting in September 2019. Other ErP relevant
information is included in the respective product data sheets.
Authorised Service Partners or installation companies can activate the cooling function via a special setting.
1 Energy efciency class scale from A++ to G.

Table of Contents

Related product manuals