106 Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Planning
107
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Planning
An overview of the said differences is shown in the following tables. The connecting conditions
for the individual devices are explained in the annexure. The required cross sections are given
in the technical specications ( 4 Technical data (split systems), p. 16, 4.6.3.3 Technical
data (compact systems), p. 50).
Split systems with combination hydro-module
Models Mains connection 1 Mains connection 2
Phases Max. current
consumption (A)
Max. power
consumption (kW)
Phases Max. current
consumption (A)
Max. power
consumption (kW)
WH-ADC0309H3E5(B) +
WH-UD03HE5-1
1 12.0 2.59 1 13.0 3.0
WH-ADC0309H3E5(B) +
WH-UD05HE5-1
1 12.0 2.59 1 13.0 3.0
WH-ADC0309H3E5(B) +
WH-UD07HE5-1
1 21.0 4.59 1 13.0 3.0
WH-ADC0309H3E5(B) +
WH-UD09HE5-1
1 22.9 5.0 1 13.0 3.0
WH-ADC1216H6E5 +
WH-UD12HE5
1 24.0 5.3 1 26.0 6.0
WH-ADC1216H6E5 +
WH-UD16HE5
1 26.0 5.74 1 26.0 6.0
WH-ADC1216H6E5 +
WH-UX09HE5
1 25.0 5.41 1 26.0 6.0
WH-ADC1216H6E5 +
WH-UX12HE5
1 29.0 6.27 1 26.0 6.0
FI protection switch and mains connections Indoor unit /outdoor unit connection
L N
L N
L
1
N
1
L
1
N
1
1 2
3
1 2
3
3
3
r
L N
L N
L
1
N
1
L
1
N
1
1 2
3
1 2
3
3
3
r
FI protection
switch
Mains connections
L N
L N
L
1
N
1
L
1
N
1
1 2
3
1 2
3
3
3
r
Mains connection 1 Mains connection 2
2
3
Terminal block strip
Indoor unit / outdoor unit
L N
L N
L
1
N
1
L
1
N
1
1 2
3
1 2
3
3
3
r
Connection of indoor unit
and outdoor unit
L N
L N
L
1
N
1
L
1
N
1
1 2
3
1 2
3
3
3
r
1
2
Terminals on indoor unit
Terminals on outdoor unit
Terminals on disconnector of the mains connection
1
2
3
Models Mains connection 1 Mains connection 2
Phases Max. current
consumption (A)
Max. power con-
sumption (kW)
Phases Max. current
consumption (A)
Max. power
consumption (kW)
WH-ADC0916H9E8 +
WH-UD09HE8
3 7.5 4.94 3 13.0 9.0
WH-ADC0916H9E8 +
WH-UD12HE8
3 8.8 5.85 3 13.0 9.0
WH-ADC0916H9E8 +
WH-UD16HE8
3 9.9 6.59 3 13.0 9.0
WH-ADC0916H9E8 +
WH-UX09HE8
3 10.4 6.85 3 13.0 9.0
WH-ADC0916H9E8 +
WH-UX12HE8
3 11.9 7.91 3 13.0 9.0
WH-ADC0916H9E8 +
WH-UX16HE8
3 15.5 10.27 3 13.0 9.0
WH-ADC0916H9E8 +
WH-UQ09HE8
3 3
WH-ADC0916H9E8 +
WH-UQ12HE8
3 3
WH-ADC0916H9E8 +
WH-UQ16HE8
3 3
FI protection switch and mains connections Indoor unit /outdoor unit connection
A1
L
A2
L
A3
N
L
L
A1
L
A2
L
A3
N
L
C1
L
C2
L
C3
N
L
C1
L
C2
L
C3
N
A1
L
A2
L
A3
N
L
L
A1
L
A2
L
A3
N
L
C1
L
C2
L
C3
N
L
C1
L
C2
L
C3
N
FI protection
switch
Mains connections
Mains connection 1 Mains connection 2
2
3
For model WH-SHF09F3E8
1
1
2
2
3
3
4
4
5
5
L
L
N
N
L
A1
L
A2
L
A3
N
L
A1
L
A2
L
A3
N
For model WH-SHF12F9E8
1
1
2
2
3
3
4
4
5
5
L
B1
L
B2
L
B3
N
L
B1
L
B2
L
B3
N
L
A1
L
A2
L
A3
N
L
A1
L
A2
L
A3
N
LN
11
N L
N L
22
POWER SUPPLY 2
LB1 LB2 LB3 N
POWER SUPPLY 1
LA1 LA2 LA3 N
45
A
Terminal block strip
Indoor unit / outdoor unit
Connection of indoor unit
and outdoor unit
1
2
Terminals on indoor unit
Terminals on outdoor unit
Terminals on disconnector of the mains connection
1
2
3
For model WH-SHF09F3E8
1
1
2
2
3
3
4
4
5
5
L
L
N
N
L
A1
L
A2
L
A3
N
L
A1
L
A2
L
A3
N
For model WH-SHF12F9E8
1
1
2
2
3
3
4
4
5
5
L
B1
L
B2
L
B3
N
L
B1
L
B2
L
B3
N
L
A1
L
A2
L
A3
N
L
A1
L
A2
L
A3
N
LN
11
N L
N L
22
P OWER S UPPLY 2
L B1 LB2 L B3 N
P OWER S UPPLY 1
L A1 LA2 L A3 N
A
1 2 3 4 5
Connection conditions
For the connection to the electricity supply, use an approved power cord with poly-
chloroprene material, symbol 60245 IEC 57 or higher, for mains connection 1 and
mains connection 2.
An approved exible cable with polychloroprene material, symbol 60245 IEC 57 is
to be used as the connecting cable between indoor and outdoor units
For combination hydro-module with the outdoor unit UD03HE5-1 or UD05HE5-1:
Mains supply 1 of this device fulls EN/ IEC 61000-3-2.
Mains supply 1 of this device fulls EN/ IEC 61000-3-3 and can be connected to
the current supply grid.
Mains supply 2 of this device fulls EN/ IEC 61000-3-2.
Mains supply 2 of this device fulls EN/ IEC 61000-3-11. A suitable voltage source
is to be connected. Its maximum allowed system impedance at the interface is Z
max
= 0.445 Ω. Connect to the EVU to ensure that the mains supply 2 is only connected
to a grid with the maximum of this impedance.