1. Vertical Airflow Direction
The louver swings up and down as shown above.
The louver does not swing when the Indoor Fan stops
during operation at the upper limit.
Heating Mode
When the intake air temp. reaches 38°C, the louver is
changed from upper to lower limit. When the intake air
temp falls to 35°C, the louver is changed from lower to
upper limit.
2. Horizontal Airflow Direction
The louver can be selected between 14° - 36° (as
shown above) when pressing Manual Airflow Direction
Selection Button.
The louver can be selected between - 61° (as shown
above) when pressing Manual Airflow Direction
Selection Button.
8.10. Airflow Direction Control
Cooling and Soft Dry Mode
The left and right airflow direction louvers can be adjusted manually.
30
CS-A7BKP CU-A7BKP5 / CS-A7BKP CU-A7BKP6 / CS-A9BKP CU-A9BKP5 / CS-A9BKP CU-A9BKP6 / CS-A12BKP CU-A12BKP5 / CS-A12BKP CU-A12BKP6