Deicing Control
Deice starts to prevent frosting at outdoor heat exchanger.
- Normal Deicing
Deice operations detection commences in Heating operation
starts or 60 minutes after previous deice operation. If the outdoor
piping temperature drops to -4°C for 50 sec. continuously during
compressor is in operation, deice will start.
(There is no detection during Outdoor Fan stops.)
- Overload Deicing
During heating operation, if the outdoor Fan OFF duration (due to
overload control) is accumulated up to 60 minutes and after
compressor starts for 1 minute, deicing starts.
- Deicing ends when
(a) 12 minutes after deicing operation starts;
(b) The outdoor piping temperature rises to about 12°C.
- After deicing operation, compressor stops for 30 seconds and 4-
way valve stays at cooling position for 10 seconds.