Air Circulation Mode Operation Time Diagram
Standard for Determining Operation Mode
8.3. Air Circulation Mode Operation
When the temperature near the ceiling reaches the setting temperature, Air Circulation Mode operation commences at low
airflow volume. It stops when the temperature drops to 2°C below the setting temperature.
8.4. Automatic Mode Operation
Indoor fan operates at SLo fan speed for 20 seconds.
After judging indoor air temperature, the operation mode is determined and operation continued at the mode determined.
After the operation mode has been determined, the mode does not change. However, Soft Dry mode operation includes
Cooling mode operation.
Room temperature adjustment.
The following are added to the setting temperature specified as above.
The mode judging temperature and standard setting temperature can be increased by 2°C, by open the circuit of JX1 at indoor
electronic controller.