74
17.2. Sensible Capacity Chart
O CS-CE7HKEW  CU-CE7HKE
O CS-CE9HKEW  CU-CE9HKE
O CS-CE12HKEW  CU-CE12HKE
230V Outdoor Temp. (qC)
Indoor wet 
bulb temp.
30 35 40 46
TCSHCIPTCSHCIPTCSHCIPTCSHCIP
17.0qC 2.03 1.54 0.43 1.90 1.48 0.46 1.77 1.42 0.50 1.61 1.35 0.53
19.0qC 2.05 0.47
19.5qC 2.23 1.61 0.44 2.09 1.55 0.47 1.94 1.49 0.50 1.77 1.42 0.54
22.0qC 2.43 1.67 0.45 2.27 1.61 0.48 2.12 1.55 0.51 1.92 1.48 0.55
230V Outdoor Temp. (qC)
Indoor wet 
bulb temp.
30 35 40 46
TCSHCIPTCSHCIPTCSHCIPTCSHCIP
17.0qC 2.58 1.96 0.54 2.41 1.88 0.58 2.24 1.80 0.62 2.04 1.71 0.67
19.0qC 2.60 0.59
19.5qC 2.83 2.05 0.55 2.65 1.97 0.59 2.46 1.89 0.63 2.24 1.80 0.68
22.0qC 3.09 2.12 0.56 2.88 2.04 0.60 2.68 1.97 0.64 2.44 1.88 0.70
230V Outdoor Temp. (qC)
Indoor wet 
bulb temp.
30 35 40 46
TCSHCIPTCSHCIPTCSHCIPTCSHCIP
17.0qC 3.47 2.63 0.84 3.24 2.52 0.91 3.02 2.43 0.97 2.74 2.30 1.05
19.0qC 3.50 0.92
19.5qC 3.81 2.76 0.86 3.56 2.65 0.92 3.31 2.55 0.99 3.01 2.43 1.07
22.0qC 4.15 2.86 0.87 3.88 2.75 0.94 3.61 2.65 1.01 3.28 2.53 1.08
TC
SHC
IP
-
-
-
Total Cooling Capacity (kW)
Sensible Heat Capacity (kW)
Input Power (kW)
Indoor 27qC/19qC
Outdoor 35qC/24qC