8
4. Repair to intrinsically safe components
• 
Do not apply any permanent inductive or 
capacitance loads to the circuit without 
ensuring that this will not exceed the 
permissible voltage and current permitted for 
the equipment in use.
• 
Intrinsically safe components are the only 
types that can be worked on while live in the 
presence of a flammable atmosphere.
• 
The test apparatus shall be at the correct 
rating.
• 
Replace components only with parts 
specified by the manufacturer. Unspecified 
parts by manufacturer may result ignition of 
refrigerant in the atmosphere from a leak.
5. Cabling
• 
Check that cabling will not be subject 
to wear, corrosion, excessive pressure, 
vibration, sharp edges or any other adverse 
environmental effects.
• 
The check shall also take into account the 
effects of aging or continual vibration from 
sources such as compressors or fans.
6. Detection of flammable refrigerants
• 
Under no circumstances shall potential 
sources of ignition be used in the searching 
or detection of refrigerant leaks.
• 
A halide torch (or any other detector using a 
naked flame) shall not be used.
7. Leak detection methods
• 
Electronic leak detectors shall be used 
to detect flammable refrigerants, but the 
sensitivity may not be adequate, or may 
need re-calibration.
(Detection equipment shall be calibrated in a 
refrigerant-free area.)
• 
Ensure that the detector is not a potential 
source of ignition and is suitable for the 
refrigerant used.
• 
Leak detection equipment shall be set at 
a percentage of the LFL of the refrigerant 
and shall be calibrated to the refrigerant 
employed and the appropriate percentage of 
gas (25 % maximum) is confirmed.
•
Leak detection fluids are suitable for use with 
most refrigerants but the use of detergents 
containing chlorine shall be avoided as the 
chlorine may react with the refrigerant and 
corrode the copper pipe-work.
• 
If a leak is suspected, all naked flames shall 
be removed/extinguished.
• 
If a leakage of refrigerant is found which 
requires brazing, all of the refrigerant shall 
be recovered from the system, or isolated 
(by means of shut off valves) in a part of the 
system remote from the leak. Oxygen free 
nitrogen (OFN) shall then be purged through 
the system both before and during the 
brazing process.
8. Removal and evacuation
•
When breaking into the refrigerant circuit to make 
repairs – or for any other purpose – conventional 
procedures shall be used.
However, it is important that best practice is 
followed since
fl
ammability is a consideration.
The following procedure shall be adhered to:
remove refrigerant -> purge the circuit with inert 
gas -> evacuate -> purge again with inert gas -> 
open the circuit by cutting or brazing
• 
The refrigerant charge shall be recovered into 
the correct recovery cylinders.
• 
The system shall be “
fl
ushed” with OFN to 
render the unit safe.
•
This process may need to be repeated several times.
• 
Compressed air or oxygen shall not be used 
for this task.
• 
Flushing shall be achieved by breaking the 
vacuum in the system with OFN and continuing 
to 
fi
ll until the working pressure is achieved, 
then venting to atmosphere, and 
fi
nally pulling 
down to a vacuum.
• 
This process shall be repeated until no 
refrigerant is within the system.
• 
When the 
fi
nal OFN charge is used, the system 
shall be vented down to atmospheric pressure 
to enable work to take place.
•
This operation is absolutely vital if brazing 
operations on the pipe work are to take place.
• 
Ensure that the outlet for the vacuum pump is 
not close to any ignition sources and there is 
ventilation available.
9. Charging procedures
• 
In addition to conventional charging procedures, 
the following requirements shall be followed.
- Ensure that contamination of different 
refrigerants does not occur when using 
charging equipment.
- Hoses or lines shall be as short as possible to 
minimize the amount of refrigerant contained 
in them.
- Cylinders shall be kept upright.
- Ensure that the refrigeration system is earthed 
prior to charging the system with refrigerant.
- Label the system when charging is complete 
(if not already).
- Extreme care shall be taken not to over 
fi
ll the 
refrigeration system.
• 
Prior to recharging the system it shall be 
pressure tested with OFN (refer to #7).
• 
The system shall be leak tested on completion 
of charging but prior to commissioning.
• 
A follow up leak test shall be carried out prior to 
leaving the site.
• 
Electrostatic charge may accumulate and 
create a hazardous condition when charging 
and discharging the refrigerant.
To avoid 
fi
re or explosion, dissipate static 
electricity during transfer by grounding and 
bonding containers and equipment before 
charging/discharging.
Safety precautions